300 questions

Water Supply and Distribution

Under IPC §605.3, water service pipe installed underground must have a working pressure rating of at least:

  • a.100 psi at 180°F
  • b.160 psi at 73°F✓
  • c.80 psi at 73°F
  • d.250 psi at 210°F

Water service pipe is rated at not less than 160 psi at 73.4°F. The 100 psi at 180°F rating applies to hot and cold water distribution pipe inside the building.IPC §605.3

Water Supply and Distribution

Hot water distribution tubing inside a building must, under IPC §605.4, be rated for at least:

  • a.50 psi at 120°F
  • b.80 psi at 140°F
  • c.160 psi at 73°F
  • d.100 psi at 180°F✓

Water distribution pipe and tubing have a minimum pressure rating of 100 psi at 180°F. The 160 psi at 73°F rating is for cold water service pipe.IPC §605.4

Water Supply and Distribution

Solder and flux used on potable water piping may contain, under IPC §605, no more than:

  • a.8.0 percent lead
  • b.2.0 percent lead
  • c.50 percent lead
  • d.0.2 percent lead✓

Solder and flux for potable water joints are limited to 0.2 percent lead; pipe and fittings are limited to a weighted average of 0.25 percent lead on wetted surfaces. The 50/50 tin-lead solder once common on water lines is prohibited.IPC §§605.2, 605.14

Water Supply and Distribution

Pipe, fittings and valves in contact with drinking water are "lead free" under IPC §605.2.1 where the weighted average lead content of wetted surfaces is not more than:

  • a.2.5 percent
  • b.8.0 percent
  • c.0.25 percent✓
  • d.0.05 percent

The limit is a weighted average of 0.25 percent lead on wetted surfaces. Eight percent was the pre-2014 federal figure; 0.2 percent applies to solder and flux.IPC §605.2.1

Water Supply and Distribution

Under IPC §606.2, where is an individual shutoff valve on the fixture supply NOT required in a dwelling?

  • a.At a bathtub or shower✓
  • b.At a lavatory
  • c.At a kitchen sink or bar sink
  • d.At a water closet

Shutoff valves are required on the supply to each fixture other than bathtubs and showers in one- and two-family residential occupancies. Water closets, lavatories and sinks each need a stop.IPC §606.2

Water Supply and Distribution

Under IPC §606.1, a full-open valve is required at each of these locations EXCEPT:

  • a.On the supply to each individual lavatory✓
  • b.On the water service at the building entrance
  • c.On the discharge side of the water meter
  • d.On the supply to each water heater

Full-open valves are required on the service at the building, on the discharge side of meters, on supplies to water heaters and tanks, and at risers in larger buildings. An individual fixture takes a shutoff valve under a different subsection, and it need not be full-open.IPC §§606.1, 606.2

Water Supply and Distribution

In the code definitions, "backsiphonage" is backflow caused by:

  • a.A water hammer surge from a quick-closing valve
  • b.Negative pressure in the potable supply piping✓
  • c.Thermal expansion in a closed water heater system
  • d.Higher pressure in the downstream system than in the supply

Backsiphonage is the backflow of contaminated water into the potable supply due to a negative or sub-atmospheric pressure in the supply pipe. Higher downstream pressure is backpressure backflow; thermal expansion and water hammer are pressure events, not definitions of backsiphonage.IPC §202

Water Supply and Distribution

Which method of backflow prevention gives the highest degree of protection and has no moving parts?

  • a.A dual check valve
  • b.A double check valve assembly
  • c.An air gap✓
  • d.An atmospheric vacuum breaker

An air gap is an unobstructed vertical distance through free atmosphere between the supply outlet and the flood rim; it cannot foul or wear. The mechanical devices all depend on checks or floats that can fail.IPC §§202, 608.14

Water Supply and Distribution

A 1/2-inch faucet spout discharges over a sink, away from any wall. Under IPC §608.15.1, the minimum air gap above the flood level rim is:

  • a.Twice the diameter of the effective opening: 1 inch✓
  • b.Six times the diameter of the effective opening: 3 inches
  • c.Four times the diameter of the effective opening: 2 inches
  • d.Equal to the diameter of the effective opening: 1/2 inch

The minimum air gap is two times the effective opening of the outlet, and more where the outlet is near walls. Two times 1/2 inch is 1 inch.IPC §608.15.1

Water Supply and Distribution

An atmospheric vacuum breaker is installed on the supply to a fixture. Under IPC §608.15.4, its critical level must be at least how far above the flood level rim of the fixture?

  • a.6 inches✓
  • b.1 inch
  • c.36 inches
  • d.12 inches

Atmospheric-type vacuum breakers are set with the critical level at least 6 inches above the flood level rim or highest downstream outlet. One inch is the fill valve figure for water closet tanks, and 12 inches applies to pressure vacuum breakers.IPC §608.15.4

Water Supply and Distribution

A pressure vacuum breaker assembly protects a lawn irrigation system. Under IPC §608.15.4, it must be installed at least how far above the highest sprinkler head or downstream pipe?

  • a.24 inches
  • b.12 inches✓
  • c.36 inches
  • d.6 inches

Pressure-type vacuum breakers are installed with the critical level at least 12 inches above all downstream piping and outlets. Six inches is the atmospheric vacuum breaker height.IPC §608.15.4

Water Supply and Distribution

Why may an atmospheric vacuum breaker not be installed with a shutoff valve downstream of it?

  • a.A downstream valve lowers the pressure below the fixture's need
  • b.A downstream valve raises the water temperature inside the body
  • c.Constant pressure holds the float closed and it can stick shut✓
  • d.Constant pressure makes the device discharge water all the time

An atmospheric vacuum breaker is for intermittent pressure only; with a valve downstream it sits under continuous pressure, and the air inlet float can stick in the closed position so it fails to open during backsiphonage. It does not discharge constantly or change pressure or temperature.IPC §608.15.4

Water Supply and Distribution

A sill cock on the outside of a house has a threaded outlet for a garden hose. Under IPC §608.15.4.2, the outlet must be protected by:

  • a.A relief valve piped to discharge on the ground
  • b.A pressure-reducing valve set at 25 psi or less at the sill cock
  • c.A vacuum breaker, such as a hose connection vacuum breaker✓
  • d.A full-port ball valve with a locking handle

Hose connections are protected by an atmospheric or pressure-type vacuum breaker or a permanently attached hose connection vacuum breaker, because a hose end left in a bucket or pool is a cross-connection. A regulator, relief valve or ball valve gives no backflow protection.IPC §608.15.4.2

Water Supply and Distribution

A lawn irrigation system injects fertiliser into the sprinkler piping. Under IPC §608.16.5, the potable supply must be protected by:

  • a.A reduced pressure principle backflow prevention assembly✓
  • b.An atmospheric vacuum breaker downstream of each zone valve
  • c.A double check valve assembly in a below-grade valve box
  • d.A single spring-loaded check valve at the water meter

Where chemicals are introduced into an irrigation system, a reduced pressure principle assembly is required. Vacuum breakers are accepted only for systems without chemical injection, and a double check or single check is not rated for a health hazard.IPC §608.16.5

Water Supply and Distribution

A hot water heating boiler containing chemical corrosion inhibitor is connected to the potable supply for make-up water. Under IPC §608.16.2, the connection is protected by:

  • a.A pressure-reducing fill valve with no added device
  • b.A reduced pressure principle backflow prevention assembly✓
  • c.A swing check valve and a gate valve installed in series
  • d.A backflow preventer with intermediate atmospheric vent

A boiler without chemicals may be protected by a backflow preventer with an intermediate atmospheric vent; where conditioning chemicals are added, a reduced pressure principle assembly or an air gap is required. Check valves and fill valves are not backflow preventers.IPC §608.16.2

Water Supply and Distribution

An automatic fire sprinkler system containing antifreeze is connected to the potable water supply. Under the IPC, the connection needs at least:

  • a.A single alarm check valve on the riser
  • b.A reduced pressure principle backflow prevention assembly✓
  • c.A double check backflow prevention assembly with test cocks
  • d.An atmospheric vacuum breaker on the riser

Sprinkler and standpipe systems are protected by a double check assembly at minimum; where the system contains chemical additives or antifreeze, a reduced pressure principle assembly is required. Vacuum breakers and an alarm check are not acceptable.IPC (2018) §608.17.4.1

Water Supply and Distribution

Which standard covers reduced pressure principle backflow prevention assemblies?

  • a.ASSE 1001
  • b.ASSE 1013✓
  • c.ASSE 1011
  • d.ASSE 1015

ASSE 1013 covers reduced pressure principle assemblies. ASSE 1001 is the atmospheric vacuum breaker, 1011 the hose connection vacuum breaker, and 1015 the double check valve assembly.IPC §608.13

Water Supply and Distribution

A carbonated beverage dispenser is connected to the water supply. Why does IPC §608.16.1 require a backflow preventer to ASSE 1022 and bar copper piping downstream of it?

  • a.Carbonated water is under vacuum and collapses copper tubing
  • b.Carbonated water leaves scale that blocks small copper tubing
  • c.Carbonated water is acidic and dissolves copper into the drink✓
  • d.Carbonated water is too cold for soldered copper joints to hold

Carbon dioxide in water forms carbonic acid, which leaches copper and can cause copper poisoning if it backs up into copper piping. The dispenser needs an ASSE 1022 backflow preventer, and piping downstream is not affected by CO2.IPC §608.16.1

Water Supply and Distribution

A reduced pressure principle assembly is to be installed. Under IPC §608.14.2, it may NOT be located:

  • a.Indoors above a floor drain sized to carry the relief discharge
  • b.In a pit or vault where the relief opening could be submerged✓
  • c.Outdoors above grade inside an insulated protective enclosure
  • d.In a mechanical room where it is accessible for yearly testing

The relief port must discharge to atmosphere through an air gap; in a pit subject to flooding the relief opening becomes a cross-connection. Indoor locations with drainage and protected above-grade enclosures are acceptable, and access for testing is required.IPC §§608.14.2, 608.15.2

Water Supply and Distribution

Nonpotable water piping in a building must be identified under IPC §608.9. Where reclaimed or rainwater is distributed, the pipe is colour-coded:

  • a.Purple✓
  • b.Green
  • c.Red
  • d.Yellow

Nonpotable water distribution piping such as reclaimed water, rainwater and gray water is purple and marked with a warning that the water is not for drinking. Yellow is associated with fuel gas marking and red with fire lines.IPC §608.9

Water Supply and Distribution

A new potable water system is disinfected under IPC §610 by filling it with a chlorine solution. Which combination satisfies the section?

  • a.50 parts per million held for 24 hours✓
  • b.5 parts per million held for 24 hours
  • c.10 parts per million held for 1 hour
  • d.50 parts per million held for 3 hours

The system is filled with a solution of at least 50 ppm chlorine for 24 hours, or 200 ppm for 3 hours, then flushed until the chlorine is purged and tested. Weaker or shorter combinations do not meet the section.IPC §610.1

Water Supply and Distribution

As an alternative to the 24-hour method, IPC §610 allows disinfection with a chlorine solution of at least 200 parts per million held for:

  • a.3 hours✓
  • b.30 minutes
  • c.12 hours
  • d.1 hour

The stronger 200 ppm solution stands in the system for 3 hours. Shorter contact times are not accepted, and 12 hours is longer than the alternative requires.IPC §610.1

Water Supply and Distribution

Under IPC §606.5, a pressure booster pump taking suction directly from the water service must have a low-pressure cutoff that stops the pump when suction pressure falls to:

  • a.2 psi
  • b.35 psi
  • c.10 psi✓
  • d.20 psi

A low-pressure cutoff prevents the booster from pulling the service below 10 psi and creating a vacuum in the main that could cause backsiphonage in neighbouring buildings. The other settings are not the code value.IPC §606.5.5

Water Supply and Distribution

A flexible braided connector supplies a lavatory faucet. Under IPC §604.5, the fixture supply may be reduced in size where the connector is no longer than:

  • a.12 inches
  • b.48 inches
  • c.30 inches✓
  • d.72 inches

The supply pipe extends to the floor or wall adjacent to the fixture, and a reduced-size flexible connector is allowed between it and the fixture where it is not more than 30 inches long. Longer small-bore connectors starve the fixture.IPC §604.5

Water Supply and Distribution

PVC water service pipe is joined with solvent cement. Under IPC §605, the joint surfaces must first be:

  • a.Roughened with a file and coated with flux
  • b.Heated with a torch until the pipe softens
  • c.Cleaned, dried and treated with a purple primer✓
  • d.Wrapped with thread seal tape for two turns

PVC pressure joints are made on clean, dry surfaces with a purple primer conforming to ASTM F656 followed by solvent cement to ASTM D2564, made while the cement is wet. Heat, flux and thread tape are for other materials.IPC §605 (PVC solvent cementing)

Water Supply and Distribution

A mechanically formed tee (a pulled branch outlet) is made in copper water tube. Under IPC §605, the branch joint must be:

  • a.Threaded
  • b.Brazed✓
  • c.Solvent cemented
  • d.Soldered

Mechanically formed tee fittings in copper tubing have a collar and a branch tube dimpled for depth control, and the joint is brazed. Soft solder is not accepted for these field-formed outlets.IPC §605 (mechanically formed tee fittings)

Water Supply and Distribution

Under IPC §608.7, a potable water outlet or stop-and-waste valve may be installed below grade only where it is:

  • a.A boiler drain installed at the lowest point of the water service
  • b.A hose bibb in a meter box that has a tight-fitting concrete cover
  • c.A drain cock that has been wrapped in polyethylene sheeting
  • d.A freezeproof yard hydrant or valve installed as the section allows✓

Potable water outlets and combination stop-and-waste valves are not installed underground or below grade, because the drain port can draw in ground water; freezeproof yard hydrants that drain the riser are allowed where the supply is protected and the hydrant is marked. A box cover or plastic wrap does not remove the hazard.IPC §608.7

Water Supply and Distribution

A water softener's drain line is run to a laundry standpipe. To protect the potable water system, the drain line must end:

  • a.In the vent pipe above the standpipe trap
  • b.Above the standpipe through an air gap✓
  • c.Inside the standpipe below the trap weir
  • d.In a tee solvent-welded into the standpipe

Water treatment units discharge through an air gap so sewage cannot be drawn back into the softener and the water supply. Any submerged or direct connection is a cross-connection, and waste never discharges into a vent.IPC §§608.1, 611

Water Supply and Distribution

Fixtures on the top floor of a building get weak flow when lower fixtures run. In sizing water piping under IPC §604, the pressure available at the highest fixture is reduced by static head at about:

  • a.0.433 psi for each foot of height✓
  • b.0.036 psi for each foot of height
  • c.2.31 psi for each foot of height
  • d.1.0 psi for each foot of height

A column of water 1 foot high exerts 0.433 psi, so each foot of elevation costs 0.433 psi (2.31 feet of head equals 1 psi). The 0.036 figure is psi per inch of water.IPC §604; Appendix E

Water Supply and Distribution

A yard hydrant line is connected to both a private well and the city water service through a normally closed gate valve. This arrangement is:

  • a.Acceptable, because the gate valve is kept closed when the well is in use
  • b.Acceptable, provided that the well water is tested for bacteria every year
  • c.Acceptable, provided that the gate valve has a lockable handle and a tag
  • d.A prohibited cross-connection between a private supply and the public system✓

Cross-connections between a private water supply and a potable public supply are prohibited; a valve is not backflow protection because it can leak or be opened. Testing and locks do not change that.IPC §608.6.2

Sanitary Drainage

Under IPC §704.1, a 2-inch horizontal drain must be installed with a uniform slope of at least:

  • a.1/2 inch per foot
  • b.1/4 inch per foot✓
  • c.1/8 inch per foot
  • d.1/16 inch per foot

Horizontal drainage pipe 2-1/2 inches and smaller slopes at least 1/4 inch per foot. One-eighth inch per foot is the minimum for 3- to 6-inch pipe and 1/16 inch per foot for 8 inches and larger.IPC §704.1

Sanitary Drainage

A 4-inch building drain is being laid. The minimum slope allowed by IPC §704.1 is:

  • a.1/8 inch per foot✓
  • b.1/4 inch per foot
  • c.1/2 inch per foot
  • d.1/16 inch per foot

Pipe from 3 to 6 inches may be laid at 1/8 inch per foot. One-quarter inch is required only for 2-1/2 inches and smaller, and 1/16 inch only for 8 inches and larger.IPC §704.1

Sanitary Drainage

A 3-inch drain runs 40 feet at the minimum slope of 1/8 inch per foot. The total fall over the run is:

  • a.10 inches
  • b.5 inches✓
  • c.2-1/2 inches
  • d.40 inches

Fall equals slope times length: 1/8 inch × 40 feet = 5 inches. Ten inches would be the fall at 1/4 inch per foot, and 2-1/2 inches at 1/16 inch per foot.IPC §704.1

Sanitary Drainage

A 2-inch drain must drop 6 inches between two points at exactly 1/4 inch per foot. How long is the run?

  • a.12 feet
  • b.48 feet
  • c.24 feet✓
  • d.18 feet

Length equals fall divided by slope: 6 inches ÷ 1/4 inch per foot = 24 feet. Forty-eight feet would be the run at 1/8 inch per foot.IPC §704.1

Sanitary Drainage

Under IPC §704.2, the size of drainage piping in the direction of flow:

  • a.May not be reduced✓
  • b.May be reduced by one pipe size at each stack
  • c.May be reduced where the slope is doubled
  • d.May be reduced downstream of each cleanout

Drainage pipe never gets smaller in the direction of flow, because solids would lodge at the reduction. A 4-by-3-inch closet bend is specifically not treated as a reduction. Slope and cleanouts do not create exceptions.IPC §704.2

Sanitary Drainage

Which fitting does IPC §706.3 allow for a change of direction from horizontal to vertical only, and not from vertical to horizontal?

  • a.A sanitary tee✓
  • b.A wye with an eighth bend
  • c.A combination wye and eighth bend
  • d.A long-sweep quarter bend

A sanitary tee has a short radius and is used only where flow turns from horizontal to vertical. Wyes, combination fittings and long sweeps may be used in any change of direction, including vertical to horizontal.IPC §706.3

Sanitary Drainage

Two water closets are set back to back on a double sanitary tee. Under IPC §706.3, this is permitted only where the horizontal developed length between each closet outlet and the fitting is at least:

  • a.36 inches
  • b.6 inches
  • c.12 inches
  • d.18 inches✓

Back-to-back water closets with pressure-assisted or similar flushing action can throw waste across a double sanitary tee; the fitting is allowed where each closet outlet is at least 18 inches of developed length from it. Otherwise a double wye pattern is used.IPC §706.3

Sanitary Drainage

Under IPC §708.1.1, cleanouts on a horizontal drain inside a building are spaced no more than:

  • a.50 feet apart
  • b.200 feet apart
  • c.150 feet apart
  • d.100 feet apart✓

Horizontal drainage pipes have cleanouts at intervals of not more than 100 feet. The other spacings are not the code figure for building drains and branches.IPC §708.1.1

Sanitary Drainage

A cleanout is required under IPC §708.1.3 near:

  • a.The junction of the building drain and the building sewer✓
  • b.The top of every vent stack where it passes through the roof
  • c.The connection of each lavatory trap arm to the wall
  • d.The midpoint of every horizontal branch over 5 feet long

A cleanout is installed at the junction of the building drain and building sewer, inside or outside the building wall. Fixture trap arms are reached through the trap, vents do not take cleanouts at the roof, and short branches do not need them at mid-length.IPC §708.1.3

Sanitary Drainage

A horizontal drain makes three 90-degree changes of direction within 30 feet. Under IPC §708.1.4, how many cleanouts are required for these changes?

  • a.Two, because cleanouts are required at alternate changes
  • b.One, because a single cleanout serves each 40 feet of run✓
  • c.None, because cleanouts are required only at stack bases
  • d.Three, because every change over 45 degrees needs its own

A cleanout is required at each change of direction greater than 45 degrees, but where more than one change occurs in a run, only one cleanout is required for each 40 feet of developed length. Three changes within 30 feet therefore need one.IPC §708.1.4

Sanitary Drainage

Under IPC §708.1.5, a cleanout on a 6-inch building sewer must be at least:

  • a.4 inches✓
  • b.6 inches
  • c.3 inches
  • d.2 inches

Cleanouts are the same nominal size as the pipe up to 4 inches; for pipes larger than 4 inches the cleanout is at least 4 inches. Two and 3 inches are too small to pass cleaning equipment for a 6-inch line.IPC §708.1.5

Sanitary Drainage

A 3-inch cleanout is installed in a mechanical room. Under IPC §708.1.9, the clearance in front of the cleanout for rodding must be at least:

  • a.18 inches✓
  • b.12 inches
  • c.36 inches
  • d.6 inches

Cleanouts on pipes 6 inches and smaller need at least 18 inches of clearance in front; cleanouts on 8-inch and larger pipes need 36 inches. Six and 12 inches do not leave room to feed a cable.IPC §708.1.9

Sanitary Drainage

In the IPC drainage fixture unit table (§709.1), a private 1.6-gallon-per-flush water closet is rated at:

  • a.2 drainage fixture units
  • b.6 drainage fixture units
  • c.3 drainage fixture units✓
  • d.1 drainage fixture unit

A 1.6 gpf private water closet carries 3 dfu and a public one 4 dfu. Lavatories are 1 dfu, and tubs, showers and kitchen sinks are 2 dfu.IPC §709.1

Sanitary Drainage

Under IPC §709.1, a lavatory is assigned how many drainage fixture units?

  • a.4
  • b.3
  • c.2
  • d.1✓

A lavatory is 1 dfu. Two dfu is the value for a bathtub, shower, kitchen sink or residential clothes washer, and 3 or 4 dfu applies to water closets.IPC §709.1

Sanitary Drainage

A fixture is not listed in the fixture unit table and has a 2-inch trap. Under IPC §709.2, its load is taken as:

  • a.5 drainage fixture units
  • b.1 drainage fixture unit
  • c.2 drainage fixture units
  • d.3 drainage fixture units✓

Unlisted fixtures are rated by trap size: 1-1/4 inch is 1 dfu, 1-1/2 inch is 2 dfu, 2 inch is 3 dfu, 2-1/2 inch is 4, 3 inch is 5 and 4 inch is 6.IPC §709.2

Sanitary Drainage

A sump pump discharges continuously into the sanitary drain at 10 gallons per minute. Under IPC §709.3, this load is counted as:

  • a.20 drainage fixture units✓
  • b.10 drainage fixture units
  • c.40 drainage fixture units
  • d.5 drainage fixture units

Continuous or semicontinuous flow is rated at 2 drainage fixture units for each gallon per minute: 10 gpm × 2 = 20 dfu. Ten dfu would be one unit per gpm, which is not the code value.IPC §709.3

Sanitary Drainage

A house has one 1.6 gpf water closet (3 dfu), one lavatory (1 dfu), one bathtub (2 dfu) and one kitchen sink (2 dfu) on a horizontal branch. The total load on the branch is:

  • a.6 drainage fixture units
  • b.8 drainage fixture units✓
  • c.10 drainage fixture units
  • d.12 drainage fixture units

Add the individual values: 3 + 1 + 2 + 2 = 8 dfu. The branch is then sized from the horizontal branch table for that load.IPC §§709.1, 710.1

Sanitary Drainage

Under the horizontal branch table of IPC §710.1, the largest load a 2-inch horizontal fixture branch may carry is:

  • a.6 drainage fixture units✓
  • b.20 drainage fixture units
  • c.3 drainage fixture units
  • d.12 drainage fixture units

A 2-inch horizontal branch is limited to 6 dfu; 1-1/2 inch carries 3, 2-1/2 inch carries 12 and 3 inch carries 20. A water closet may not discharge into a branch smaller than 3 inches.IPC §710.1

Sanitary Drainage

A below-grade bathroom drains to a sewage ejector. Under IPC §712.2, the ejector's discharge pipe must be fitted with:

  • a.A check valve and a full-open valve on the discharge side of the check✓
  • b.A vacuum breaker and a relief valve at the top of the discharge riser
  • c.A pressure-reducing valve and a strainer on the discharge side of it
  • d.A trap and a cleanout between the pump and the gravity building drain

The discharge has a check valve to stop backflow into the sump and a full-open valve downstream of it so the check and pump can be serviced. Regulators, vacuum breakers and traps are not used on ejector discharge piping.IPC §712.2

Sanitary Drainage

Under IPC §712.3.2, a sewage sump pit must be at least:

  • a.36 inches in diameter and 60 inches deep
  • b.24 inches in diameter and 48 inches deep
  • c.12 inches in diameter and 12 inches deep
  • d.18 inches in diameter and 24 inches deep✓

The sump pit is not less than 18 inches in diameter and 24 inches deep unless otherwise approved, and it has a gastight removable cover and a vent. The other sizes are not the code minimum.IPC §712.3.2