409 questions

Renewable Energy Technologies

Three PV circuits share a common-return conductor. The individual circuits are protected by overcurrent devices rated 15 A, 15 A, and 20 A. What is the minimum ampacity of the common-return conductor?

  • a.35 A
  • b.50 A✓
  • c.62.5 A
  • d.78.1 A

A common-return conductor must have an ampacity at least equal to the sum of the overcurrent device ratings of the individual circuits. 15 A + 15 A + 20 A = 50 A. 35 A leaves one circuit out, and 62.5 A and 78.1 A add 125% multipliers that this rule does not require. See 690.8(C).2026 NEC §690.8(C)

Renewable Energy Technologies

PV circuit conductors run inside a building in a raceway and have overcurrent protection at one end only. Up to what conductor length is this arrangement permitted?

  • a.1.8 m (6 ft)
  • b.3 m (10 ft)✓
  • c.7.5 m (25 ft)
  • d.15 m (50 ft)

Conductors in a building may be protected at one end only when they are no longer than 3 m (10 ft) and are in a raceway or metal-clad cable. Longer runs need protection at both ends or must meet one of the other listed arrangements. The 6 ft value is shorter than the limit, and 25 ft and 50 ft exceed it. See 690.9(A)(3).2026 NEC §690.9(A)(3)

Renewable Energy Technologies

Equipment that interconnects a power production source so it runs in parallel with the primary source must meet which requirement?

  • a.Be rated at 125% of the service rating
  • b.Be approved by the utility in place of listing
  • c.Be listed or field labeled for the interactive function✓
  • d.Be marked as suitable for stand-alone use only

Interconnection and interactive equipment must be listed for the interactive function, or be evaluated for that function and carry a field label, or both. Utility approval does not replace this, and equipment for stand-alone use only is not intended to run in parallel with another source. The 125% answer borrows a sizing idea that has nothing to do with listing. See 705.2.2026 NEC §705.2

Renewable Energy Technologies

Four dc-to-dc converters are connected in series in a PV circuit. Each has a maximum rated output voltage of 80 V, and the listing instructions give no method for finding the circuit voltage. What is the maximum voltage of this converter circuit?

  • a.80 V
  • b.320 V✓
  • c.400 V
  • d.500 V

For converters wired in series, the maximum voltage follows the listing instructions. When the instructions give no method, it is the sum of the maximum rated output voltages of the series converters. 4 x 80 V = 320 V. 80 V treats the string as a single converter, and 400 V and 500 V add multipliers the rule does not use. See 690.7(B)(2).2026 NEC §690.7(B)(2)

Renewable Energy Technologies

At a commercial parking facility with permanently connected EVSE, the required emergency shutoff must be in sight of the equipment and within what distance range from it?

  • a.3.0 m (10 ft) to 15.0 m (50 ft)
  • b.6.0 m (20 ft) to 30.0 m (100 ft)✓
  • c.7.5 m (25 ft) to 23.0 m (75 ft)
  • d.15.0 m (50 ft) to 45.0 m (150 ft)

For locations other than one- and two-family dwellings, the emergency shutoff must be readily accessible, in sight of the equipment, and not less than 6.0 m (20 ft) nor more than 30.0 m (100 ft) from it. The other ranges do not appear in this rule. See 625.43(D)(1).2026 NEC §625.43(D)(1)

Renewable Energy Technologies

Fixed EVSE that is not specifically listed and marked for its location is installed outdoors. What is the minimum height above grade for storing the coupling means?

  • a.300 mm (12 in.)
  • b.450 mm (18 in.)
  • c.600 mm (24 in.)✓
  • d.900 mm (36 in.)

Unless the equipment is specifically listed and marked for the location, the coupling means must be stored at least 600 mm (24 in.) above grade outdoors. The 450 mm (18 in.) figure is the indoor height above the floor. The other two values are not in the rule. See 625.50.2026 NEC §625.50

Renewable Energy Technologies

Which receptacles installed for connecting electric vehicle charging equipment need GFCI protection for personnel?

  • a.Only 125-volt, 15- and 20-ampere receptacles
  • b.Only receptacles located outdoors
  • c.Only receptacles in dwelling unit garages
  • d.All receptacles installed for EV charging✓

Every receptacle installed for the connection of electric vehicle charging must have ground-fault circuit-interrupter protection for personnel. The rule is not limited by voltage, ampere rating, or location, so each of the narrower answers leaves some charging receptacles unprotected. See 625.54.2026 NEC §625.54

Renewable Energy Technologies

A receptacle outlet that is part of electric vehicle power export equipment may be rated up to 250 volts, single phase. What is its maximum ampere rating?

  • a.50 A✓
  • b.60 A
  • c.80 A
  • d.100 A

Receptacle outlets used with electric vehicle power export equipment are limited to 250 volts, single phase, and 50 amperes. The larger ratings exceed that limit. See 625.60(B).2026 NEC §625.60(B)

Renewable Energy Technologies

An installer wants to put a 50-ampere receptacle for cord-and-plug-connected EVSE on a 40-ampere branch circuit, as the general receptacle rating table referenced in 210.24 would otherwise allow. What does Article 625 say?

  • a.Permitted where the EVSE draws 32 A or less
  • b.Permitted only at one-family dwellings
  • c.Permitted where GFCI protection is added
  • d.Not permitted for EVSE receptacles✓

Article 625 overrides the general table for this case: a 50-ampere receptacle for EVSE may not go on a 40-ampere branch circuit. The rule has no allowance based on charger current, occupancy type, or added GFCI protection. See 625.44.2026 NEC §625.44