409 questions

Motors and Generators

For a torque motor, which current is treated as the rated current when sizing the branch-circuit conductors?

  • a.The table full-load current for its horsepower
  • b.The locked-rotor current marked on its nameplate✓
  • c.The nameplate current multiplied by 150 percent
  • d.The service-factor current from the nameplate

A torque motor normally operates at standstill, so its rated current is its locked-rotor current, and that nameplate value is used for the branch-circuit conductors. The horsepower tables are for general motors and do not apply here. The 150 percent multiplier belongs to the adjustable-voltage motor rule, and service-factor current is not used for conductor sizing. See 430.6(B).2026 NEC §430.6(B)

Motors and Generators

One feeder supplies only three continuous-duty, three-phase, 460-volt motors: 15 hp, 10 hp and 7 1/2 hp. Table 430.250 lists their full-load currents as 21, 14 and 11 amperes. What is the minimum ampacity of the feeder conductors?

  • a.46 A
  • b.48.75 A
  • c.49.5 A
  • d.51.25 A✓

A feeder for several motors needs 125 percent of the full-load current of the highest rated motor plus the full-load currents of the others. Working: 21 x 1.25 = 26.25, then 26.25 + 14 + 11 = 51.25 amperes. The 46 ampere value is the plain sum with no increase, and the two middle values put the 25 percent on the wrong motor. See 430.24.2026 NEC §430.24

Motors and Generators

A 15 hp, 230-volt, three-phase squirrel-cage motor has a table full-load current of 42 amperes. Using Table 430.52(C)(1) and the standard ratings in Table 240.6(A), what is the maximum standard dual-element time-delay fuse for the branch-circuit short-circuit protection, assuming the motor starts normally?

  • a.70 A
  • b.80 A✓
  • c.90 A
  • d.110 A

The table allows a dual-element time-delay fuse at 175 percent of full-load current: 42 x 1.75 = 73.5 amperes. That is not a standard rating, so the next higher standard size, 80 amperes, is permitted. The 70 ampere answer rounds down when rounding up is allowed, 90 amperes uses the higher limit reserved for a motor that will not start, and 110 amperes uses the breaker percentage. See 430.52(C)(1) and Table 240.6(A).2026 NEC §430.52(C)(1)

Motors and Generators

A 50 hp, 460-volt, three-phase motor has a table full-load current of 65 amperes. The inverse-time breaker sized from Table 430.52(C)(1) trips on starting. What is the largest standard inverse-time breaker that may be used?

  • a.175 A
  • b.200 A
  • c.250 A✓
  • d.300 A

When the table value will not start the motor, an inverse-time breaker may be increased, but never above 400 percent of full-load current where that current is 100 amperes or less. Working: 65 x 4 = 260 amperes, and this ceiling may not be exceeded, so the largest standard size is 250 amperes. The 175 ampere answer is the normal table size, 200 amperes applies the 300 percent limit meant for motors over 100 amperes, and 300 amperes rounds up past the ceiling. See 430.52(C)(1).2026 NEC §430.52(C)(1)

Motors and Generators

A feeder supplies only three 460-volt, three-phase motors with full-load currents of 40, 27 and 14 amperes. Their branch-circuit breakers are 100, 70 and 35 amperes. What is the largest standard feeder overcurrent device permitted?

  • a.125 A✓
  • b.150 A
  • c.175 A
  • d.200 A

The feeder device may not exceed the largest branch-circuit short-circuit device plus the full-load currents of the other motors: 100 + 27 + 14 = 141 amperes. This is a maximum with no allowance to round up, so the largest standard rating is 125 amperes. The 150 ampere answer rounds up, and the larger values add a 125 percent factor or the other breaker ratings, which the rule does not use. See 430.62(A).2026 NEC §430.62(A)

Motors and Generators

A continuous-duty motor has a nameplate full-load current of 18 amperes, a marked service factor of 1.0 and a marked temperature rise of 50°C. What is the maximum setting of its separate overload device?

  • a.20.7 A✓
  • b.22.5 A
  • c.23.4 A
  • d.25.2 A

A separate overload device is set from the nameplate current. The 125 percent allowance needs a service factor of 1.15 or more or a temperature rise of 40°C or less, and this motor has neither, so 115 percent applies: 18 x 1.15 = 20.7 amperes. The 22.5 ampere answer uses 125 percent, and the two highest values use the larger percentages that apply only when the motor cannot start. See 430.32(A)(1).2026 NEC §430.32(A)(1)

Motors and Generators

A 10 hp, 240-volt dc motor has a table full-load current of 38 amperes and is fed from a single-phase full-wave rectifier. What is the minimum ampacity of the conductors between the rectifier and the motor?

  • a.38 A
  • b.47.5 A
  • c.57 A✓
  • d.72.2 A

Rectified single-phase power has a high ripple, so the conductors between the rectifier and a dc motor are sized at 150 percent of full-load current for a full-wave bridge. Working: 38 x 1.5 = 57 amperes. The 47.5 ampere answer uses the ordinary 125 percent rule, 72.2 amperes uses the 190 percent half-wave figure, and 38 amperes applies no increase. See 430.22(A).2026 NEC §430.22(A)

Motors and Generators

A motor in an intermittent-duty application has a 15-minute time rating and a nameplate current of 40 amperes. Using Table 430.22(E), what is the minimum ampacity of its branch-circuit conductors?

  • a.34 A✓
  • b.36 A
  • c.48 A
  • d.56 A

For duty-cycle service the conductor size is a percentage of the nameplate current that depends on the type of duty and the time rating of the motor. Intermittent duty with a 15-minute rated motor is 85 percent: 40 x 0.85 = 34 amperes. The other values come from the periodic duty row, the short-time or varying duty rows, and the continuous-rated motor column. See Table 430.22(E).2026 NEC Table 430.22(E)

Electrical Control Devices and Disconnecting Means

A motor disconnecting means must have an ampere rating of at least what percent of the motor full-load current?

  • a.125%
  • b.115%✓
  • c.100%
  • d.110%

The disconnecting means for a motor must be rated at least 115% of the motor full-load current.2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

The disconnecting means for air-conditioning and refrigerating equipment must be located:

  • a.only at the main service panel of the building, wherever it sits
  • b.at least 25 ft from the unit
  • c.inside a locked room
  • d.within sight from and readily accessible to it✓

2026 NEC 440.14 requires the disconnect to be within sight from and readily accessible from the equipment. Trap: locating it only at the service panel does not satisfy the within-sight requirement for the unit.2026 NEC §440.14

Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Electrical Control Devices and Disconnecting Means

Under 2026 NEC 110.22, each disconnecting means must be:

  • a.legibly marked to indicate its purpose unless located and arranged so the purpose is evident✓
  • b.installed only by the utility
  • c.rated at least 100 A
  • d.painted red

110.22(A): each disconnecting means must be legibly marked to indicate its purpose unless it is located and arranged so the purpose is evident.2026 NEC §110.22(A)

Electrical Control Devices and Disconnecting Means

An individual disconnecting means is provided for a 480-volt motor controller. Where must that disconnecting means be located?

  • a.Within 25 ft of the panelboard that supplies the motor
  • b.In sight from the controller location✓
  • c.In the same room as the driven machinery
  • d.Anywhere on the premises if it can be locked open

Section 430.102(A) calls for a disconnecting means for each motor controller, placed in sight from the controller location. The trap is tying the location to the supply panelboard or the driven machine. The machinery matters for the motor disconnect in 430.102(B), not for the controller disconnect.2026 NEC §430.102(A)

Electrical Control Devices and Disconnecting Means

A motor circuit has two disconnecting means, one at the controller and one at the motor. How many of them must be readily accessible?

  • a.Neither one, if both can be locked open
  • b.Only the one mounted nearest the motor
  • c.At least one of them✓
  • d.Both of them in every installation

Section 430.107 requires at least one of the disconnecting means to be readily accessible. It does not say which one, so it need not be the one nearest the motor. A lock-open provision does not remove the requirement.2026 NEC §430.107

Electrical Control Devices and Disconnecting Means

A 150 hp ac stationary motor is to have a general-use or isolating switch as its disconnecting means. What condition makes this permitted?

  • a.The switch is rated at twice the motor full-load current
  • b.The switch is mounted within 10 ft of the motor terminals
  • c.The switch is horsepower rated at half the motor rating
  • d.The switch is plainly marked not to be operated under load✓

For stationary motors above 100 hp ac (or above 40 hp dc), 430.109(E) permits a general-use or isolating switch only when it is plainly marked to warn against operating it under load. The twice-full-load-current idea belongs to the small-motor rule in 430.109(C).2026 NEC §430.109(E)

Electrical Control Devices and Disconnecting Means

A listed manual motor controller is installed between the final motor branch-circuit short-circuit protective device and the motor, and it is used as the motor disconnecting means. What additional marking must it carry?

  • a.That it is suitable as a motor disconnect✓
  • b.That it is suitable for use as service equipment
  • c.That it must not be operated while under load
  • d.That it is limited to group motor installations

Section 430.109(A)(6) accepts a listed manual motor controller as a disconnecting means in that position only if it is additionally marked as suitable for use as a motor disconnect. A warning against operating under load is the marking for isolating switches on very large motors, a different rule.2026 NEC §430.109(A)(6)

Electrical Control Devices and Disconnecting Means

A motor controller is marked with a slash voltage rating of 480Y/277 V. On which circuit is it permitted to be applied?

  • a.A solidly grounded circuit with no more than 277 V to ground and 480 V between conductors✓
  • b.An ungrounded delta circuit with no more than 480 V between any two conductors
  • c.A corner-grounded delta circuit with no more than 480 V between any two conductors
  • d.Any circuit, grounded or not, with no more than 480 V between any two conductors

Section 430.83(E) limits a slash-rated controller to solidly grounded circuits where the voltage to ground does not exceed the lower number and the voltage between any two conductors does not exceed the higher number. On an ungrounded or corner-grounded 480 V delta, the voltage to ground can reach 480 V, so only a controller with a straight 480 V rating fits there.2026 NEC §430.83(E)

Electrical Control Devices and Disconnecting Means

Which statement is correct for a motor controller that does not also serve as the disconnecting means?

  • a.It must open every ungrounded conductor to the motor
  • b.It must open the grounded conductor before the others
  • c.It must open the equipment grounding conductor as well
  • d.It need not open all conductors to the motor✓

Section 430.84 says a controller is not required to open all conductors to the motor. That is why a separate disconnecting means, which does open all ungrounded supply conductors, is required. The trap is applying the disconnect rule to the controller.2026 NEC §430.84

Electrical Control Devices and Disconnecting Means

The disconnecting means for a rooftop refrigeration unit is readily accessible to unqualified persons. An enclosure door or hinged cover that exposes energized parts when open must be:

  • a.Painted red and marked with the circuit voltage
  • b.Interlocked with the compressor contactor coil
  • c.Removed and replaced with a dead-front cover
  • d.Locked or require a tool to open✓

Section 440.11 says that where the disconnecting means is readily accessible to unqualified persons, any enclosure door or hinged cover that exposes energized parts when open must be locked or need a tool to open. Color, signs, or interlocks are not what this rule asks for.2026 NEC §440.11

Electrical Control Devices and Disconnecting Means

In a commercial building, an outdoor disconnecting means supplies a split-system heat pump. What must the outdoor disconnect be marked with?

  • a.The location of all indoor units it supplies✓
  • b.The refrigerant type and charge of the system
  • c.The available fault current and the date it was found
  • d.The name of the contractor who installed the system

Section 440.15 applies to split-system HVAC equipment in other than one- and two-family dwellings. The outdoor disconnecting means must be marked to show where every indoor unit it supplies is located. Fault current marking is a service and panelboard matter, not this rule.2026 NEC §440.15

Electrical Control Devices and Disconnecting Means

As a general rule, where must the service disconnect for a one-family dwelling be installed?

  • a.In a readily accessible indoor location nearest the service conductor entrance
  • b.In a readily accessible outdoor location on or within sight of the dwelling✓
  • c.In any accessible location inside an attached garage
  • d.In the basement within 10 ft of the meter socket

Section 230.70(A)(1) puts the service disconnect for one- and two-family dwellings in a readily accessible outdoor location, either on the dwelling or within sight of it. The indoor location nearest the point of entrance is the choice allowed for other occupancies under 230.70(A)(2), and that is the trap here.2026 NEC §230.70(A)(1)

Electrical Control Devices and Disconnecting Means

A power-operated circuit breaker is permitted as the service disconnecting means for the ungrounded service conductors provided that it:

  • a.Can be opened by hand if the power supply fails✓
  • b.Recloses by itself when the power is restored
  • c.Is rated at 125 percent of the calculated load
  • d.Is controlled only from a remote location

Section 230.76 allows either a manually operable switch or breaker, or a power-operated one that can still be opened by hand if its power supply fails. A device that could only be operated electrically, or only from a remote station, could not be opened in an outage.2026 NEC §230.76

Electrical Control Devices and Disconnecting Means

A feeder supplies a detached building, and the building disconnecting means is installed outside the building. As a general rule, where must it be located?

  • a.At a readily accessible location on or within sight of the building✓
  • b.At the panelboard where the feeder originates
  • c.At any point on the premises that can be locked
  • d.At the first pole or pull box along the feeder

Section 225.31(B) says that a building disconnecting means located outside must be at a readily accessible location on the building or within sight of it as defined in 110.29. The breaker back at the supply panelboard does not satisfy this by itself.2026 NEC §225.31(B)

Electrical Control Devices and Disconnecting Means

The emergency disconnect for a one-family dwelling must be marked on the outside front of its enclosure. What colors and minimum letter height apply to that marking?

  • a.White background, red text, letters at least 1/2 in. high
  • b.Red background, white text, letters at least 1/4 in. high
  • c.Red background, white text, letters at least 1/2 in. high✓
  • d.Yellow background, black text, letters at least 1 in. high

Section 225.41(C) requires the emergency disconnect marking to be on the outside front of the enclosure with a red background and white text, in letters at least 1/2 in. (13 mm) high. Reversing the colors or shrinking the letters is the trap.2026 NEC §225.41(C)

Electrical Control Devices and Disconnecting Means

A feeder overcurrent device supplying a building is not readily accessible. Which statement describes the branch-circuit overcurrent devices that must then be installed on its load side?

  • a.Readily accessible and of the same ampere rating
  • b.Readily accessible and of a lower ampere rating than the feeder device✓
  • c.Lockable and of a higher ampere rating
  • d.Reachable by ladder and of any ampere rating

Section 225.40 says that when the feeder overcurrent device is not readily accessible, branch-circuit overcurrent devices must be installed on the load side, mounted in a readily accessible location, and have a lower ampere rating than the feeder device. The lower rating is what makes the accessible device the one that opens first.2026 NEC §225.40

Electrical Control Devices and Disconnecting Means

A motor disconnecting means has a current rating of 100 A. Applying the general current-rating rule for motor circuits rated 1000 volts or less, which of these is the highest motor full-load current it can serve?

  • a.71 A
  • b.77 A
  • c.83 A✓
  • d.88 A

Section 430.110(A) requires the disconnect rating to be at least 115 percent of the motor full-load current. Working backward, 100 A / 1.15 = 86.96 A, so the motor current cannot exceed about 86.9 A. Check: 83 A x 1.15 = 95.45 A, which fits, while 88 A x 1.15 = 101.2 A, which is over 100 A.2026 NEC §430.110(A)

Electrical Control Devices and Disconnecting Means

One disconnecting means serves a combination load that operates together: a motor with a full-load current of 34 A, a second motor with a full-load current of 21 A, and a resistance heater drawing 15 A. What is the minimum ampere rating of the disconnecting means?

  • a.63.25 A
  • b.70 A
  • c.78.5 A
  • d.80.5 A✓

Section 430.110(C)(2) sets the ampere rating at not less than 115 percent of the sum of all currents at the full-load condition, resistance loads included. Sum: 34 + 21 + 15 = 70 A. Then 70 x 1.15 = 80.5 A. Leaving the heater out of the sum, or adding 25 percent to only the largest motor as in conductor sizing, gives the wrong figures.2026 NEC §430.110(C)(2)

Electrical Control Devices and Disconnecting Means

A stationary 1/2 hp, 115-volt motor has a full-load current of 9.8 A. If a general-use switch is used as its disconnecting means, what is the minimum ampere rating of the switch?

  • a.11.27 A
  • b.19.6 A✓
  • c.24.5 A
  • d.29.4 A

For stationary motors of 2 hp or less and 300 volts or less, 430.109(C)(1) permits a general-use switch with an ampere rating of at least twice the motor full-load current. 9.8 A x 2 = 19.6 A. Using 115 percent (11.27 A) applies the general disconnect rating rule, not the general-use switch rule.2026 NEC §430.109(C)(1)

Electrical Control Devices and Disconnecting Means

A small motor that is not covered by the Code motor current tables has a full-load current of 2.4 A. When rating a disconnecting means for a combination load, what locked-rotor current is assumed for this motor?

  • a.2.4 A
  • b.3 A
  • c.7.2 A
  • d.14.4 A✓

Section 430.110(C)(3) says that for small motors not covered by the motor current tables, the locked-rotor current is assumed to be six times the full-load current. 2.4 A x 6 = 14.4 A. Using three times (7.2 A) or adding only 25 percent (3 A) understates the starting current.2026 NEC §430.110(C)(3)

Electrical Control Devices and Disconnecting Means

A hermetic refrigerant motor-compressor has a nameplate rated-load current of 22 A and a branch-circuit selection current of 27 A. What is the minimum ampere rating of its disconnecting means?

  • a.25.3 A
  • b.27 A
  • c.31.05 A✓
  • d.40.5 A

Section 440.12(A)(1) requires an ampere rating of at least 115 percent of the rated-load current or the branch-circuit selection current, whichever is greater. The larger value is 27 A, so 27 x 1.15 = 31.05 A. Using the 22 A rated-load current (25.3 A) ignores the larger branch-circuit selection current.2026 NEC §440.12(A)(1)

Electrical Control Devices and Disconnecting Means

One disconnecting means serves a packaged unit with a compressor rated-load current of 18 A, a fan motor full-load current of 3 A, and a resistance heater drawing 9 A, all of which can operate at the same time. What is the minimum ampere rating of the disconnecting means?

  • a.30 A
  • b.32.7 A
  • c.34.5 A✓
  • d.37.5 A

For combination loads, 440.12(B)(2) requires an ampere rating of at least 115 percent of the sum of all currents at the rated-load condition. Sum: 18 + 3 + 9 = 30 A. Then 30 x 1.15 = 34.5 A. Applying the 115 percent to the compressor alone (32.7 A) or using 125 percent as for conductors (37.5 A) are the common slips.2026 NEC §440.12(B)(2)

Electrical Control Devices and Disconnecting Means

The service to a one-family dwelling has a calculated load of 85 A, and its service disconnecting means consists of two circuit breakers. One breaker is rated 60 A. What is the minimum rating of the second breaker so that the combined rating meets the required minimum for this service?

  • a.15 A
  • b.25 A
  • c.40 A✓
  • d.60 A

Section 230.79 requires a rating not less than the calculated load and, for a one-family dwelling, not less than 100 A, so the required minimum is 100 A. Section 230.80 lets the ratings of multiple breakers be combined to reach it. 100 A - 60 A = 40 A. Subtracting from the 85 A calculated load (25 A) forgets the 100 A dwelling floor.2026 NEC §230.80

Special Occupancies, Equipment, and Conditions

A location where ignitable concentrations of flammable gases or vapors exist under normal operating conditions is classified as:

  • a.Class II, Division 1
  • b.Class I, Division 2
  • c.Class I, Division 1✓
  • d.Class III

Class I covers flammable gases/vapors; Division 1 means ignitable concentrations can exist under normal operation, so it is Class I, Division 1.2026 NEC §500.5(B)(1)

Special Occupancies, Equipment, and Conditions

A location made hazardous by combustible dust is classified as which class?

  • a.Class I
  • b.Class IV
  • c.Class III
  • d.Class II✓

Class II locations are those hazardous because of the presence of combustible dust.2026 NEC §500.5(C)

Special Occupancies, Equipment, and Conditions

In a Class I, Division 1 location, a sealing fitting must be installed within what distance of an enclosure containing arcing devices?

  • a.18 in✓
  • b.24 in
  • c.12 in
  • d.36 in

Seals are required within 18 in of enclosures that contain devices which may produce arcs, sparks, or high temperatures.2026 NEC §501.15(A)(1)

Special Occupancies, Equipment, and Conditions

The equipotential bonding grid around a permanently installed pool must use a solid copper conductor no smaller than:

  • a.#4 AWG
  • b.#8 AWG✓
  • c.#6 AWG
  • d.#10 AWG

Pool equipotential bonding must use an insulated, covered, or bare solid copper conductor not smaller than #8 AWG.2026 NEC §680.26(B)

Special Occupancies, Equipment, and Conditions

Where a permanently installed pool is installed, the required 125-volt, 15- or 20-ampere general-purpose receptacle must be located not less than what distance from the inside pool wall?

  • a.5 ft
  • b.8 ft
  • c.10 ft
  • d.6 ft✓

At a permanently installed pool, at least one such receptacle is required not less than 6 ft and not more than 20 ft from the inside wall, and not more than 6 ft 6 in. above the floor, platform or grade serving the pool. The minimum setback is 6 ft.2026 NEC §680.22(A)(1)

Special Occupancies, Equipment, and Conditions

A wet-niche underwater luminaire supplied with sinusoidal ac and operating without GFCI protection is limited to a maximum of:

  • a.24 V
  • b.15 V✓
  • c.120 V
  • d.30 V

Underwater luminaires that operate above the low-voltage contact limit need GFCI protection (2026 NEC 680.23(A)(3)). Article 100 sets that limit at 15 V RMS for sinusoidal ac. The 30 V figure applies only to continuous dc.2026 NEC §680.23(A)(3)

Special Occupancies, Equipment, and Conditions

Which wiring method is acceptable in a Class I, Division 2 location?

  • a.Type AC with standard fittings
  • b.Nonmetallic-sheathed (Romex) cable
  • c.Type MC with listed fittings✓
  • d.Type NM with standard connectors

Type MC cable terminated with listed fittings is among the wiring methods listed for Class I, Division 2 in 2026 NEC Table 501.10(B)(1). Ordinary Type NM and Type AC cable are not listed.2026 NEC Table 501.10(B)(1)

Special Occupancies, Equipment, and Conditions

Atmospheres containing acetylene are classified in which hazardous (classified) location group?

  • a.Group D
  • b.Group A✓
  • c.Group C
  • d.Group B

2026 NEC 500.6(A)(1) places acetylene in Group A. Trap: Group D, whose typical material is propane, is a different group; acetylene has a group of its own.2026 NEC §500.6(A)(1)

Special Occupancies, Equipment, and Conditions

In patient care spaces, branch-circuit wiring to receptacles and fixed equipment must provide grounding by:

  • a.an insulated EGC plus the metal raceway or cable armor✓
  • b.the metal raceway or cable armor alone serving as the only ground path
  • c.an isolated ground connection only
  • d.the grounded (neutral) conductor

2026 NEC 517.13 requires two grounding paths: a metal raceway or cable armor that qualifies as an equipment grounding conductor, and an insulated copper equipment grounding conductor. Trap: the raceway alone is not sufficient in patient care spaces.2026 NEC §517.13

Special Occupancies, Equipment, and Conditions

A location where ignitable concentrations of flammable gas or vapor are present only under abnormal (fault or leak) conditions is classified as:

  • a.Class I, Division 1
  • b.Class I, Division 2✓
  • c.Class III
  • d.Class II, Division 1

2026 NEC 500.5(B)(2): Class I, Division 2 covers flammable gases or vapors that are normally confined and are present only under abnormal conditions such as a leak or rupture.2026 NEC §500.5(B)(2)

Special Occupancies, Equipment, and Conditions

A location where ignitible fibers/flyings are handled, manufactured, or used is classified as:

  • a.Class IV
  • b.Class II
  • c.Class I
  • d.Class III✓

2026 NEC 500.5(D): locations made hazardous by ignitible fibers/flyings are Class III. Note that combustible metal fibers/flyings are treated as Class II, Division 1, Group E.2026 NEC §500.5(D)

Special Occupancies, Equipment, and Conditions

Atmospheres containing propane fall into which hazardous-location group?

  • a.Group D✓
  • b.Group B
  • c.Group A
  • d.Group C

2026 NEC 500.6(A)(4): propane is the typical Class I, Group D material. Acetylene is Group A, hydrogen is typical of Group B, and ethylene is typical of Group C.2026 NEC §500.6(A)(4)

Special Occupancies, Equipment, and Conditions

In a Class I, Division 1 location, where a conduit leaves the classified area into an unclassified area, a seal is required:

  • a.never, if rigid metal conduit is used
  • b.only at the service equipment
  • c.only if the conduit is over 2 in trade size
  • d.within 10 ft of the boundary, with no coupling or fitting between the seal and the boundary except as permitted✓

2026 NEC 501.15(A)(4): a seal is required within 10 ft of the boundary where conduit leaves a Class I, Division 1 location, with no unions, couplings, boxes, or fittings between the seal and the boundary other than a listed explosionproof reducer at the seal.2026 NEC §501.15(A)(4)

Special Occupancies, Equipment, and Conditions

Luminaires and lighting outlets installed over a permanently installed pool must be mounted at least what height above the maximum water level (for new installations without special protection)?

  • a.8 ft
  • b.12 ft✓
  • c.10 ft
  • d.5 ft

2026 NEC 680.22(B)(1): luminaires over the pool, or over the area within 5 ft horizontally of its inside walls, must be at least 12 ft above the maximum water level. Lower heights apply only to GFCI-protected indoor equipment and to existing installations.2026 NEC §680.22(B)(1)

Special Occupancies, Equipment, and Conditions

The equipotential bonding required around a permanently installed pool must extend horizontally what distance from the inside pool wall?

  • a.5 ft
  • b.2 ft
  • c.3 ft✓
  • d.6 ft

2026 NEC 680.26(B)(2): the bonded perimeter surface extends 3 ft horizontally beyond the inside walls of the pool.2026 NEC §680.26(B)(2)

Special Occupancies, Equipment, and Conditions

An emergency system must be capable of supplying power to its loads within what maximum time after normal supply is lost?

  • a.120 seconds
  • b.10 seconds✓
  • c.60 seconds
  • d.30 seconds

Emergency systems must restore power to life-safety loads within 10 seconds of loss of the normal source.2026 NEC §700.12

Special Occupancies, Equipment, and Conditions

An ammonia refrigeration machinery room has adequate mechanical ventilation that is started by a detection system. For the room to be treated as unclassified, the detection system must start the ventilation at a concentration not exceeding:

  • a.25 ppm
  • b.50 ppm
  • c.150 ppm✓
  • d.300 ppm

Section 500.5(A)(2) lets an ammonia machinery room be unclassified when its mechanical ventilation either runs continuously or is started by a detection system at no more than 150 ppm. The lower figures are stricter than the Code asks, and 300 ppm would start the fans too late to qualify.2026 NEC §500.5(A)(2)

Special Occupancies, Equipment, and Conditions

In a metal finishing shop, aluminum dust could be present in hazardous quantities, but only when the dust collection system malfunctions. Which classification applies?

  • a.Class II, Division 1✓
  • b.Class II, Division 2
  • c.Class III, Division 1
  • d.Class I, Division 2

Section 500.5(C)(1) makes a location Class II, Division 1 wherever Group E dusts, which are the combustible metal dusts such as aluminum, may be present in hazardous quantities under normal or abnormal conditions. Dust present only through abnormal operation would otherwise point to Division 2, but that does not apply to metal dust. Class III is for fibers and flyings and Class I is for gases and vapors.2026 NEC §500.5(C)(1)

Special Occupancies, Equipment, and Conditions

A flammable gas other than acetylene has a maximum experimental safe gap (MESG) of 0.40 mm. Which Class I group applies to it?

  • a.Group A
  • b.Group B✓
  • c.Group C
  • d.Group D

Section 500.6(A) puts a gas in Group B when its MESG is 0.45 mm or less. A value of 0.40 mm is under that limit, so the gas is Group B. Group A is reserved for acetylene, Group C covers MESG values above 0.45 mm up to 0.75 mm, and Group D covers values above 0.75 mm.2026 NEC §500.6(A)