What is the minimum required width of working space in front of electrical equipment?
- a.36 in. in every case, regardless of equipment width
- b.24 in. or the depth of the equipment, whichever is greater
- c.18 in. or half the width of the equipment, whichever is less
- d.30 in or the width of the equipment, whichever is greater✓
The working space width must be at least 30 in or the width of the equipment, whichever is greater, and must permit a 90-degree door opening.2026 NEC §110.26(A)(2)
What is the minimum headroom (height) of working space about electrical equipment such as panelboards?
- a.8 ft
- b.6 ft
- c.6.5 ft✓
- d.7 ft
The minimum headroom of working space is 6.5 ft (or the height of the equipment, whichever is greater).2026 NEC §110.26(A)(3)
The dedicated equipment space above a panelboard extends how far above the equipment (or to a structural ceiling if lower)?
- a.4.5 ft
- b.7 ft
- c.6 ft✓
- d.3 ft
Under 110.26(E)(1)(a) the dedicated electrical space is the width and depth of the equipment, from the floor to 6 ft above the equipment or to the structural ceiling if that is lower. Piping, ducts and other foreign equipment are kept out of this zone.2026 NEC §110.26(E)(1)(a)
Equipment over 6 ft wide that contains overcurrent, switching, or control devices needs an entrance to and egress from the working space at each end when it is rated at what current or more?
- a.1000 A
- b.600 A
- c.1200 A✓
- d.800 A
Under 110.26(C)(2), equipment rated 1,200 A or more and over 6 ft wide needs an entrance to and egress from the working space at each end, unless one of the single-entrance conditions in that section is met.2026 NEC §110.26(C)(2)
Equipment operating at 151-600 V to ground under Condition 3 requires what minimum depth of working space?
- a.3 ft
- b.3.5 ft
- c.4 ft✓
- d.5 ft
Table 110.26(A)(1): for 151-600 V to ground, Condition 3 (live parts on both sides of the working space) requires 4 ft. Trap: 3 ft is the Condition 1 value at this voltage.2026 NEC Table 110.26(A)(1)
For equipment operating at 151-600 V to ground under Condition 2, what is the minimum depth of working space in front of the equipment?
- a.5 ft
- b.3.5 ft✓
- c.4 ft
- d.3 ft
Table 110.26(A)(1): for 151-600 V to ground, Condition 2 (live parts on one side, grounded parts on the other) requires 3 ft 6 in. (3.5 ft) of clear working depth.2026 NEC Table 110.26(A)(1)
For equipment operating at 0-150 V to ground, what is the minimum depth of working space regardless of condition?
- a.3 ft✓
- b.3.5 ft
- c.2.5 ft
- d.4 ft
Table 110.26(A)(1): at 0-150 V to ground the working depth is 3 ft for Conditions 1, 2, and 3.2026 NEC Table 110.26(A)(1)
Personnel doors for electrical equipment rated at what current or more must open in the direction of egress and be equipped with panic hardware?
- a.800 A✓
- b.1,000 A
- c.1,200 A
- d.600 A
110.26(C)(3): where equipment rated 800 A or more has a personnel door less than 25 ft from the nearest edge of the working space, the door must open at least 90 degrees in the direction of egress and have listed panic hardware or listed fire exit hardware.2026 NEC §110.26(C)(3)
Under 2026 NEC 408.4(A), every circuit and circuit modification in a panelboard must be:
- a.numbered only, with no written description of the load served
- b.identified in the directory only where the circuit is rated over 100 A
- c.legibly identified as to its clear, evident, and specific purpose in a circuit directory✓
- d.identified in the directory only where the circuit supplies a motor
408.4(A): each circuit and circuit modification needs a legible, permanent description that is clear, evident, and specific to its purpose. For a panelboard the description goes in a circuit directory at the panel.2026 NEC §408.4(A)
Under 2026 NEC 110.26, the working space in front of energized electrical equipment must:
- a.be reduced to 24 in for panelboards
- b.be kept clear and not be used for storage✓
- c.double as an egress corridor only
- d.be usable for storage when de-energized
110.26(B): the required working space must not be used for storage. When normally enclosed live parts are exposed for inspection or servicing in a passageway or general open space, the working space must be suitably guarded.2026 NEC §110.26(B)
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
For equipment operating at 151-600 V to ground under Condition 1, what is the minimum depth of working space?
- a.3 ft✓
- b.4 ft
- c.2.5 ft
- d.3.5 ft
Table 110.26(A)(1): at 151-600 V to ground, Condition 1 (no live or grounded parts on the other side of the working space) requires 3 ft of working depth.2026 NEC Table 110.26(A)(1)
A panelboard is rated 225 A. What is the maximum rating of the overcurrent device that may protect it?
- a.225 A✓
- b.200 A
- c.400 A
- d.250 A
Each panelboard must be protected by an overcurrent device rated no more than the panelboard rating, so 225 A is the maximum.2026 NEC §408.36
Which of the following is the next standard overcurrent device rating above 95 A?
- a.90 A
- b.125 A
- c.110 A
- d.100 A✓
Standard ratings include 90, 100, 110, and 125 A. The next standard size above 95 A is 100 A.2026 NEC Table 240.6(A)
What is the maximum rating of the overcurrent device that may protect a 400-A-rated panelboard?
- a.350 A
- b.450 A
- c.400 A✓
- d.500 A
2026 NEC 408.36: a panelboard must be protected by an overcurrent device rated no more than the panelboard rating, so 400 A is the maximum.2026 NEC §408.36
Receptacles are not permitted inside a tub or shower space or within a zone around it. Measured horizontally from the outside edge of a bathtub, and vertically from the floor to a height above the top of the tub rim, how far does that zone extend?
- a.2 ft horizontally and 6 ft vertically
- b.5 ft horizontally and 8 ft vertically
- c.6 ft horizontally and 7 ft vertically
- d.3 ft horizontally and 8 ft vertically✓
Section 406.9(C)(1) keeps receptacles out of the tub or shower space and out of a zone that reaches 3 ft horizontally from the outside edge of the tub or shower and vertically from the floor to 8 ft above the top of the tub rim or shower stall threshold. The zone takes in the space directly over the tub or shower as well. The other pairs of numbers do not appear in this rule.2026 NEC §406.9(C)(1)
A two-wire nongrounding receptacle on a circuit with no equipment grounding conductor is replaced with a GFCI-type receptacle. What marking is required on the GFCI receptacle or its cover plate?
- a.GFCI Protected Outlet
- b.No Equipment Ground✓
- c.Ungrounded Circuit Only
- d.Two-Wire Supply Only
Section 406.12(D)(2)(b) allows a nongrounding receptacle to be replaced with a GFCI-type receptacle where no means of attaching to an equipment grounding conductor exists in the enclosure, and the receptacle or its cover plate must be marked to show there is no equipment ground. The equipment grounding terminal must not be connected from that GFCI receptacle to any outlet it supplies. The marking tells the user that the grounding slot is not connected to ground.2026 NEC §406.12(D)(2)(b)
What is the minimum thickness permitted for a receptacle faceplate made of ferrous metal?
- a.0.015 in.
- b.0.020 in.
- c.0.030 in.✓
- d.0.040 in.
Section 406.16(A) requires metal faceplates to be at least 0.030 in. thick if ferrous metal and at least 0.040 in. thick if nonferrous metal. Steel is ferrous, so 0.030 in. applies. The 0.040 in. figure is the trap, because it belongs to brass, aluminum, and other nonferrous plates.2026 NEC §406.16(A)
A wall-mounted luminaire is to be supported on a box that is not designed for luminaire support. This is permitted if the luminaire is secured to the box with at least two No. 6 or larger screws and weighs not more than:
- a.6 lb✓
- b.15 lb
- c.35 lb
- d.50 lb
Section 314.27(A)(1)(a) allows a wall-mounted luminaire or lampholder weighing not more than 6 lb to be supported on other boxes, such as a device box, when it is secured with no fewer than two No. 6 or larger screws. The 50 lb figure is the weight a box designed for luminaires is expected to carry, so it does not apply to an ordinary device box.2026 NEC §314.27(A)(1)(a)
The mounting screws that came with a listed receptacle are lost. What may be used instead to attach the receptacle to the box?
- a.Sheet metal screws with 18 threads per inch
- b.Drywall screws at least 1-1/4 in. long
- c.Machine screws with 32 threads per inch✓
- d.Self-tapping screws with 24 threads per inch
Section 406.14 requires the screws that attach a receptacle to a box to be the type supplied with the listed receptacle, or machine screws having 32 threads per inch. Machine screws of that thread match the tapped holes in the box. Drywall and sheet metal screws cut their own coarse thread and damage those holes.2026 NEC §406.14
A piece of utilization equipment mounts on an outlet box and projects 2-1/8 in. rearward from the mounting plane of the box. What is the minimum internal depth of the box?
- a.2-1/8 in.
- b.2-3/8 in.✓
- c.2-5/8 in.
- d.3-1/8 in.
Where equipment projects more than 1-7/8 in. rearward from the mounting plane, 314.24(B)(1) requires a box depth of at least the depth of the equipment plus 1/4 in. Here that is 2-1/8 + 1/4 = 2-3/8 in. A box exactly as deep as the equipment leaves none of the extra space the rule calls for.2026 NEC §314.24(B)(1)
A 62-lb chandelier will hang below a standard ceiling outlet box. The box is not listed for more than the minimum weight required of a ceiling luminaire box. How must the chandelier be supported?
- a.Supported independently of the ceiling outlet box✓
- b.Hung from the box with two No. 6 screws
- c.Hung from any listed ceiling outlet box
- d.Supported by the raceway entering the box
A ceiling luminaire box only has to carry 50 lb. Under 314.27(A)(2), a luminaire over 50 lb must be supported independently of the outlet box unless the box is listed for at least the weight to be supported. At 62 lb and with a box not listed for that weight, the chandelier needs its own support from the structure. Two No. 6 screws are the method for a wall luminaire of 6 lb or less.2026 NEC §314.27(A)(2)
An old house has two-wire circuits with no equipment grounding conductor. An electrician installs a GFCI receptacle at the first outlet and replaces three downstream nongrounding receptacles with ordinary grounding-type receptacles fed from its load side. What must be marked on the three downstream receptacles or their cover plates?
- a."GFCI Protected" only
- b."No Equipment Ground" only
- c."Isolated Ground" and "GFCI Protected"
- d."GFCI Protected" and "No Equipment Ground"✓
Section 406.12(D)(2) allows nongrounding receptacles to be replaced with grounding-type receptacles where they are supplied through a GFCI, and those receptacles or their cover plates must carry both markings: that they are GFCI protected and that there is no equipment ground. No equipment grounding conductor is connected between them. The single marking about no equipment ground is for the GFCI receptacle itself, not for the grounding-type receptacles it feeds.2026 NEC §406.12(D)(2)
A single hermetic refrigerant motor-compressor has a rated-load current of 24 A. What minimum branch-circuit conductor ampacity is required?
- a.30 A✓
- b.24 A
- c.28 A
- d.36 A
Conductors to a single motor-compressor must be at least 125% of the rated-load or branch-circuit selection current: 24 x 1.25 = 30 A.2026 NEC §440.32
A hermetic motor-compressor has a rated-load current of 24 A. Applying 440.22(A) Exception No. 1 (next higher standard rating permitted), what is the maximum branch-circuit short-circuit and ground-fault device at 175%?
- a.40 A
- b.60 A
- c.45 A✓
- d.50 A
175% of 24 A is 42 A, which is not a standard rating. Exception No. 1 to 2026 NEC 440.22(A) allows the next higher standard rating, and Table 240.6(A) lists 45 A. Without the exception the device could not exceed 42 A.2026 NEC §440.22(A)
An air-conditioning unit is multimotor and combination-load equipment. Which value marked on it sets the minimum ampacity of the conductors supplying it?
- a.Maximum overcurrent protection
- b.Rated-load amps only
- c.Nameplate horsepower
- d.Minimum circuit ampacity✓
Conductors supplying multimotor and combination-load equipment must have an ampacity of at least the minimum circuit ampacity marked on the equipment (2026 NEC 440.35). The rule names that marking only; rated-load amps alone, horsepower and the maximum overcurrent protection marking are not what it uses.2026 NEC §440.35
A motor without a marked service factor (or with a service factor under 1.15) and without a marked temperature rise has a nameplate full-load current of 28 A. What is the maximum overload protection at 115%?
- a.30 A
- b.35 A
- c.28 A
- d.32.2 A✓
For motors without a marked service factor of 1.15 or greater and without a marked temperature rise of 40 C or less, the overload device is limited to 115% of nameplate full-load current (2026 NEC 430.32(A)(1)): 28 x 1.15 = 32.2 A.2026 NEC §430.32(A)(1)
How many overload (running-protection) units are required for a three-phase AC motor?
- a.1
- b.2
- c.3✓
- d.4
2026 NEC Table 430.37 calls for three overload units, one in each phase, for a three-phase AC motor. Trap: one or two units apply to single-phase and two-phase arrangements, not to three-phase motors.2026 NEC Table 430.37
A single hermetic refrigerant motor-compressor has a rated-load current of 28 A. What minimum branch-circuit conductor ampacity is required?
- a.35 A✓
- b.28 A
- c.40 A
- d.31.5 A
2026 NEC 440.32: conductors to a single motor-compressor need at least 125% of the rated-load current: 28 x 1.25 = 35 A.2026 NEC §440.32
A hermetic motor-compressor has a rated-load current of 28 A. Applying 440.22(A) Exception No. 1 (next higher standard rating permitted), what is the maximum branch-circuit short-circuit and ground-fault device at 175%?
- a.50 A✓
- b.40 A
- c.45 A
- d.60 A
175% of 28 A is 49 A, which is not a standard rating. Exception No. 1 to 2026 NEC 440.22(A) allows the next higher standard rating, and Table 240.6(A) lists 50 A. Without the exception the device could not exceed 49 A.2026 NEC §440.22(A)
An A/C unit has a compressor rated-load current of 20 A and a fan motor of 3 A. What minimum branch-circuit conductor ampacity is required?
- a.30 A
- b.25 A
- c.28 A✓
- d.23 A
2026 NEC 440.33: add the compressor rated-load current, the other motor current, and 25% of the largest: 20 + 3 + (0.25 x 20) = 28 A.2026 NEC §440.33
A motor marked with a temperature rise of 40 C (and no service factor) has a nameplate full-load current of 52 A. What is the maximum overload protection?
- a.52 A
- b.59.8 A
- c.65 A✓
- d.60 A
2026 NEC 430.32(A)(1): for a motor marked with a temperature rise of 40 C or less, the overload device may be set at up to 125% of nameplate full-load current: 52 x 1.25 = 65 A.2026 NEC §430.32(A)(1)
Per 430.6(A), which current value is used to size the conductors and the branch-circuit short-circuit and ground-fault protection for a general-application motor?
- a.the nameplate full-load current, not the table current
- b.the service-factor amperes marked on the nameplate
- c.the locked-rotor current from the motor nameplate
- d.the table full-load current, not the nameplate current rating✓
2026 NEC 430.6(A)(1): for general motor applications, the full-load current values in Tables 430.247 through 430.250, not the nameplate current, are used to size conductors and short-circuit and ground-fault protection. Separate overload protection uses the nameplate current.2026 NEC §430.6(A)(1)
From the motor full-load current table, what is the full-load current of a 25-HP, 460-V, three-phase induction motor?
- a.28 A
- b.42 A
- c.34 A✓
- d.40 A
In the 460-volt column of the induction-motor section, a 25-HP motor is listed at 34 A. Table full-load current (FLC), not nameplate, is used for conductor and protection sizing.2026 NEC Table 430.250
A single continuous-duty motor has a table full-load current of 34 A. What minimum conductor ampacity is required for its branch circuit?
- a.50 A
- b.34 A
- c.40 A
- d.42.5 A✓
Motor branch-circuit conductors must be at least 125% of the FLC: 34 A x 1.25 = 42.5 A minimum ampacity.2026 NEC §430.22
A motor with a service factor of 1.15 has a nameplate full-load current of 34 A. What is the maximum overload protection setting at 125%?
- a.42.5 A✓
- b.45.9 A
- c.34 A
- d.39.1 A
Under 2026 NEC 430.32(A)(1), a motor with a marked service factor of 1.15 or greater may have its overload device set at up to 125% of nameplate full-load current: 34 x 1.25 = 42.5 A. Trap: 39.1 A uses the 115% limit that applies to motors without that service factor or temperature-rise marking.2026 NEC §430.32(A)(1)
For a motor with a 34-A full-load current, what is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection (250%, then next higher standard size)?
- a.70 A
- b.100 A
- c.90 A✓
- d.80 A
2026 NEC Table 430.52(C)(1) allows an inverse-time breaker at 250% of full-load current: 34 x 2.50 = 85 A. That is not a standard rating, so 430.52(C)(1)(a) permits the next higher standard rating from Table 240.6(A), which is 90 A.2026 NEC Table 430.52(C)(1)
A feeder supplies three motors with full-load currents of 34 A, 28 A, and 22 A. What minimum conductor ampacity is required for the feeder?
- a.110 A
- b.92.5 A✓
- c.105 A
- d.84 A
Feeder ampacity = 125% of the largest motor FLC plus the sum of the others: (34 x 1.25) + 28 + 22 = 42.5 + 50 = 92.5 A.2026 NEC §430.24
A commercial service supplies several motors; the largest has a 40-A full-load current. How much is added to the service calculation for the largest-motor factor?
- a.50 A
- b.40 A
- c.10 A✓
- d.8 A
2026 NEC 430.24 (reached through 120.50) takes the highest rated motor at 125% and the others at 100%, so 25% of the largest motor FLC is added on top of the motor loads: 0.25 x 40 = 10 A. Trap: 50 A adds 125% of the motor, double-counting the FLC that is already in the load.2026 NEC §430.24
From the motor full-load current table, what is the full-load current of a 50-HP, 460-V, three-phase induction motor?
- a.52 A
- b.80 A
- c.65 A✓
- d.48 A
2026 NEC Table 430.250 lists 65 A for a 50-HP, 460-V three-phase motor. This table FLC (not nameplate) is used for branch-circuit and feeder sizing. Trap: 52 A is the 40-HP value.2026 NEC Table 430.250
A motor with a 34-A full-load current is protected by a non-time-delay (one-time) fuse. At 300%, what is the maximum branch-circuit short-circuit/ground-fault fuse (next standard size)?
- a.90 A
- b.100 A
- c.125 A
- d.110 A✓
2026 NEC Table 430.52(C)(1) allows 300% for non-time-delay fuses: 34 x 3.00 = 102 A. Where this is not a standard rating, 430.52(C)(1)(a) permits the next higher standard fuse, 110 A. Trap: a time-delay (dual-element) fuse uses only 175% (59.5 A, so 60 A).2026 NEC Table 430.52(C)(1)
A 40-HP, 460-V, three-phase induction motor has a table full-load current of 52 A. What minimum branch-circuit conductor ampacity is required?
- a.52 A
- b.50 A
- c.65 A✓
- d.72 A
2026 NEC 430.22: motor branch-circuit conductors must be at least 125% of the table FLC: 52 x 1.25 = 65 A.2026 NEC §430.22
A 30-HP, 460-V, three-phase motor has a table full-load current of 40 A. What is the maximum inverse-time circuit breaker for branch-circuit short-circuit and ground-fault protection?
- a.100 A✓
- b.90 A
- c.125 A
- d.110 A
2026 NEC Table 430.52(C)(1): an inverse-time breaker is allowed at 250% of full-load current: 40 x 2.50 = 100 A, which is a standard rating in Table 240.6(A).2026 NEC Table 430.52(C)(1)
A 30-HP, 460-V, three-phase motor has a table full-load current of 40 A. What is the maximum time-delay (dual-element) fuse for branch-circuit short-circuit/ground-fault protection?
- a.80 A
- b.90 A
- c.60 A
- d.70 A✓
2026 NEC Table 430.52(C)(1): time-delay fuses at 175% of FLC = 40 x 1.75 = 70 A, which is a standard rating in Table 240.6(A).2026 NEC Table 430.52(C)(1)
A motor with a service factor of 1.15 has a nameplate full-load current of 40 A. What is the maximum overload protection at 125% of nameplate?
- a.46 A
- b.54 A
- c.44 A
- d.50 A✓
2026 NEC 430.32(A)(1): motors with a marked service factor of 1.15 or more may have overload protection set at 125% of nameplate full-load current: 40 x 1.25 = 50 A.2026 NEC §430.32(A)(1)
A feeder supplies a 50-HP (65 A) and a 30-HP (40 A) motor, both 460-V three-phase. What minimum feeder conductor ampacity is required?
- a.131.25 A
- b.121.25 A✓
- c.105 A
- d.115 A
2026 NEC 430.24: 125% of the largest motor FLC plus the sum of the others: (65 x 1.25) + 40 = 81.25 + 40 = 121.25 A.2026 NEC §430.24
A motor feeder's largest branch-circuit short-circuit device is 110 A; the other motors on the feeder total 68 A of full-load current. What is the maximum standard-rating feeder short-circuit/ground-fault device?
- a.150 A
- b.200 A
- c.178 A
- d.175 A✓
2026 NEC 430.62(A): the feeder device may not exceed the largest branch device (110 A) plus the other full-load currents (68 A) = 178 A. Rounding up is not allowed here, so the largest standard rating in Table 240.6(A) not exceeding 178 A is 175 A.2026 NEC §430.62(A)
A generator has no overcurrent protection of its own. The conductors from its terminals to the first distribution device containing overcurrent protection must have an ampacity of at least what percent of the nameplate current?
- a.100%
- b.125%
- c.110%
- d.115%✓
Where overcurrent protection is not provided at the generator, the conductors from its terminals to the first distribution device containing overcurrent protection must be at least 115% of the nameplate current rating.2026 NEC §445.13(A)
A three-phase motor is connected wye-start, delta-run. The conductors between the controller and the motor must have an ampacity of at least what percentage of the motor full-load current?
- a.50%
- b.62.5%
- c.72%✓
- d.125%
For a wye-start, delta-run motor, the conductors on the load side of the controller are sized at 72 percent of the motor full-load current, because each set carries only part of the line current. The 125 percent figure is the general single-motor rule and applies on the line side of the controller. The 62.5 percent figure belongs to part-winding motors, and 50 percent is not a conductor multiplier for either connection. See 430.22(C).2026 NEC §430.22(C)
A continuous-duty motor has an integral thermal protector and a table full-load current of 8 amperes. The ultimate trip current of the protector may not exceed what percentage of that full-load current?
- a.125%
- b.140%
- c.156%
- d.170%✓
For a thermal protector that is integral with the motor, the limit depends on the table full-load current: 170 percent where it does not exceed 9 amperes. The 156 percent value applies from 9.1 through 20 amperes and 140 percent applies above 20 amperes. The 125 percent figure is for separate overload devices and is based on nameplate current. See 430.32(A)(2).2026 NEC §430.32(A)(2)
According to Table 430.52(C)(1), an inverse-time circuit breaker used as the branch-circuit short-circuit and ground-fault protective device for a wound-rotor motor may be rated at no more than what percentage of the motor full-load current?
- a.150%✓
- b.175%
- c.250%
- d.300%
The wound-rotor row of the table limits an inverse-time breaker to 150 percent of full-load current. The 250 percent figure is the inverse-time breaker value for squirrel-cage and synchronous motors, 175 percent is the dual-element fuse value for those motors, and 300 percent is their nontime-delay fuse value. See Table 430.52(C)(1).2026 NEC Table 430.52(C)(1)