A 400-A feeder overcurrent device supplies a 10-ft tap. Under the 10-ft feeder tap rule, what minimum tap-conductor ampacity comes from the 1/10 provision?
- a.200 A
- b.133 A
- c.13 A
- d.40 A✓
2026 NEC 240.21(B)(1) requires a 10-ft tap that leaves the enclosure where it is made to have an ampacity of at least 1/10 of the feeder overcurrent device rating: 400 / 10 = 40 A (and at least the load served). Trap: 133 A is the 1/3 value that belongs to the 25-ft tap rule in 240.21(B)(2).2026 NEC §240.21(B)(1)
A 600-A feeder overcurrent device supplies a 25-ft tap. Under the 25-ft feeder tap rule, what minimum tap-conductor ampacity is required?
- a.60 A
- b.200 A✓
- c.300 A
- d.150 A
2026 NEC 240.21(B)(2) requires the 25-ft tap ampacity to be at least 1/3 of the 600-A device: 600 / 3 = 200 A. Trap: 60 A applies the 1/10 figure, which belongs to the 10-ft tap rule in 240.21(B)(1).2026 NEC §240.21(B)(2)
A feeder supplies five household electric ranges, each rated 12 kW. Using Column C of the range demand table, what is the demand load?
- a.17,000 VA
- b.25,000 VA
- c.20,000 VA✓
- d.21,000 VA
2026 NEC Table 120.55, Column C, gives 20 kW for five ranges not over 12 kW: 20,000 VA. Trap: 21,000 VA is the six-range value; 25,000 VA wrongly prorates 5 x 5 kW.2026 NEC Table 120.55
A dwelling has 9,000 VA general lighting, 3,000 VA small-appliance, and 1,500 VA laundry. Applying the standard general-lighting demand (first 3,000 VA at 100%, remainder at 35%), what is the net general lighting load?
- a.6,675 VA✓
- b.7,275 VA
- c.13,500 VA
- d.4,725 VA
Sum = 9,000 + 3,000 + 1,500 = 13,500 VA. First 3,000 at 100% = 3,000; remaining 10,500 at 35% = 3,675. Net = 6,675 VA (2026 NEC Table 120.45).2026 NEC Table 120.45
Using Column C of the household-range demand table, what is the demand load for three 12-kW electric ranges served by one feeder?
- a.11,000 VA
- b.16,000 VA
- c.12,000 VA
- d.14,000 VA✓
2026 NEC Table 120.55, Column C, gives 14 kW for three ranges not over 12 kW: 14,000 VA.2026 NEC Table 120.55
A single household electric range is rated 14 kW. Using the 5%-per-kW-over-12 rule on the 8-kW Column C base, what is the demand load?
- a.10,000 VA
- b.9,600 VA
- c.8,800 VA✓
- d.8,000 VA
2026 NEC Table 120.55, Note 1: 14 kW is 2 kW over 12, so add 5% x 2 = 10% to the 8-kW Column C value: 8,000 x 1.10 = 8,800 VA.2026 NEC Table 120.55
A dwelling feeder supplies four electric clothes dryers, each rated 5.5 kW. Applying the dryer demand factor, what is the demand load?
- a.17,600 VA✓
- b.22,000 VA
- c.20,000 VA
- d.16,500 VA
2026 NEC Table 120.54 takes three to five dryers at 80%. 4 x 5,500 = 22,000 VA connected; 22,000 x 0.80 = 17,600 VA.2026 NEC Table 120.54
A feeder supplies five electric clothes dryers, each rated 5 kW. Applying the dryer demand factor for five dryers, what is the demand load?
- a.20,000 VA✓
- b.25,000 VA
- c.21,250 VA
- d.18,750 VA
2026 NEC Table 120.54 takes three to five dryers at 80%: 5 x 5,000 x 0.80 = 20,000 VA.2026 NEC Table 120.54
A dwelling has five fastened-in-place appliances (dishwasher 1,200, disposal 900, water heater 4,500, compactor 1,000, wine cooler 600 VA) totaling 8,200 VA. What is the demand after the fastened-appliance factor?
- a.6,560 VA
- b.8,200 VA
- c.4,100 VA
- d.6,150 VA✓
2026 NEC 120.53 permits a 75% demand factor for four or more fastened-in-place appliances on the same feeder: 8,200 x 0.75 = 6,150 VA.2026 NEC §120.53
Under the optional dwelling method, the general loads (lighting, small-appliance, laundry, appliances, range) total 32,000 VA. Applying 120.82(B) (100% of the first 8 kVA, 40% of the remainder), what is the demand?
- a.12,800 VA
- b.17,600 VA✓
- c.18,800 VA
- d.32,000 VA
2026 NEC 120.82(B): 8,000 + 0.40 x 24,000 = 8,000 + 9,600 = 17,600 VA. The first 8 kVA stays at 100%.2026 NEC §120.82(B)
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
Under the optional dwelling method a home has 5,000 VA of air-conditioning and 9,000 VA of central electric space heating (not run together). What single value is included for the heating/cooling load?
- a.5,000 VA
- b.5,850 VA✓
- c.9,000 VA
- d.14,000 VA
2026 NEC 120.82(C) takes the largest of the listed heating and cooling figures: A/C at 100% = 5,000 VA versus central electric heat at 65% = 5,850 VA. The larger, 5,850 VA, is used.2026 NEC §120.82(C)
A 48-unit multifamily building has 720,000 VA of connected load and an applicable Table 120.84(C) demand factor of 26%. What is the calculated demand load?
- a.230,400 VA
- b.720,000 VA
- c.187,200 VA✓
- d.288,000 VA
2026 NEC 120.84 multiplies the connected load by the Table 120.84(C) demand factor, which is 26% for 46 to 50 dwelling units: 720,000 x 0.26 = 187,200 VA.2026 NEC Table 120.84(C)
Three 12-kW household ranges on a feeder have a Column C demand of 14,000 VA. Using the range neutral allowance, what is the range contribution to the feeder neutral?
- a.8,400 VA
- b.11,000 VA
- c.14,000 VA
- d.9,800 VA✓
2026 NEC 120.61(B)(1) allows the feeder neutral for household ranges at 70% of the range demand: 14,000 x 0.70 = 9,800 VA.2026 NEC §120.61(B)(1)
A feeder neutral carries a maximum unbalanced load of 300 A. Applying the neutral demand allowance, what is the calculated neutral load?
- a.300 A
- b.250 A
- c.235 A
- d.270 A✓
2026 NEC 120.61(B)(2): 70% applies to the portion over 200 A: 200 + 0.70 x 100 = 200 + 70 = 270 A.2026 NEC §120.61(B)(2)
An office has a 10,800-VA general receptacle load. Applying the demand (first 10 kVA at 100%, remainder at 50%), what is the demand load?
- a.10,800 VA
- b.10,000 VA
- c.5,400 VA
- d.10,400 VA✓
2026 NEC 120.47 and Table 120.47: first 10,000 VA at 100% + remaining 800 VA at 50% = 10,000 + 400 = 10,400 VA.2026 NEC Table 120.47
A commercial kitchen has eight kitchen-equipment units totaling 80 kW. Applying the demand factor for six or more units, what is the demand load?
- a.45 kW
- b.60 kW
- c.52 kW✓
- d.48 kW
2026 NEC Table 120.56 allows 65% for six or more units of kitchen equipment: 80 x 0.65 = 52 kW.2026 NEC Table 120.56
An 800-A feeder overcurrent device supplies a 25-ft tap. Under the 25-ft feeder tap rule, what minimum tap-conductor ampacity is required?
- a.80 A
- b.160 A
- c.266.7 A✓
- d.200 A
2026 NEC 240.21(B)(2): the 25-ft tap ampacity must be at least 1/3 of the 800-A device: 800 / 3 = 266.7 A. Trap: 80 A uses the 1/10 figure from the 10-ft tap rule.2026 NEC §240.21(B)(2)
A 600-A feeder overcurrent device supplies a 10-ft tap. Under the 10-ft feeder tap rule, what minimum ampacity comes from the 1/10 provision?
- a.40 A
- b.60 A✓
- c.200 A
- d.133 A
2026 NEC 240.21(B)(1): a 10-ft tap that leaves the enclosure where it is made must have an ampacity of at least 1/10 of the 600-A device: 600 / 10 = 60 A (and at least the load served). Trap: 200 A is the 1/3 value from the 25-ft tap rule.2026 NEC §240.21(B)(1)
A feeder supplies a 100-A continuous load and a 50-A noncontinuous load. What minimum conductor ampacity is required?
- a.187.5 A
- b.175 A✓
- c.150 A
- d.200 A
2026 NEC 215.4(A)(1): 125% of the continuous load plus 100% of the noncontinuous load: (100 x 1.25) + 50 = 125 + 50 = 175 A.2026 NEC §215.4(A)(1)
A feeder supplies a 120-A continuous load and a 40-A noncontinuous load. What is the minimum standard overcurrent device rating?
- a.225 A
- b.190 A
- c.175 A
- d.200 A✓
2026 NEC 215.5: the device must be rated at least 125% of the continuous load plus the noncontinuous load = (120 x 1.25) + 40 = 190 A. The next standard rating in Table 240.6(A) is 200 A.2026 NEC §215.5
A feeder supplies six household clothes dryers, each rated 5 kW. Applying the dryer demand factor for six dryers, what is the demand load?
- a.18,000 VA
- b.25,500 VA
- c.22,500 VA✓
- d.30,000 VA
2026 NEC Table 120.54 lists 75% for six dryers: 6 x 5,000 x 0.75 = 22,500 VA.2026 NEC Table 120.54
A feeder supplies five household electric ranges, each rated 14 kW. Using Column C plus the over-12-kW adjustment, what is the demand load?
- a.20,000 VA
- b.22,000 VA✓
- c.24,000 VA
- d.25,000 VA
2026 NEC Table 120.55, Column C, for five ranges = 20 kW; Note 1 adds 5% per kW over 12 (14 kW is 2 over): 20,000 x 1.10 = 22,000 VA.2026 NEC Table 120.55
A feeder is protected by a 400-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#6 AWG
- b.#4 AWG
- c.#1 AWG
- d.#3 AWG✓
For a 400-A overcurrent device the table requires #3 Cu for the equipment grounding conductor.2026 NEC Table 250.122
Two paralleled sets of 500-kcmil Cu (75 C, 380 A each) supply one feeder. What is the combined ampacity before adjustment?
- a.620 A
- b.760 A✓
- c.380 A
- d.500 A
Paralleled conductor ampacities add: 380 A x 2 = 760 A total for the feeder.2026 NEC Table 310.16
A feeder is protected by a 200-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#6 AWG✓
- b.#4 AWG
- c.#8 AWG
- d.#10 AWG
2026 NEC Table 250.122: for an overcurrent device rated not more than 200 A, the minimum copper equipment grounding conductor is 6 AWG.2026 NEC Table 250.122
A feeder is protected by a 600-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#1 AWG✓
- b.#3 AWG
- c.#2 AWG
- d.1/0 AWG
2026 NEC Table 250.122: for an overcurrent device rated not more than 600 A, the minimum copper equipment grounding conductor is 1 AWG.2026 NEC Table 250.122
A feeder supplies a detached building. Under 2026 NEC 250.32, the feeder must include which of the following?
- a.an equipment grounding conductor run with the feeder to the building✓
- b.a separate utility service
- c.no grounding conductor if the feeder is under 100 A
- d.a bonded neutral serving as the only ground path
2026 NEC 250.32(B)(1) requires an equipment grounding conductor run with the supply conductors to the separate building. The neutral is kept isolated from the equipment grounding conductor and the electrodes at that building.2026 NEC §250.32(B)(1)
A conductor has an allowable ampacity of 240 A, which is not a standard rating. Under the next-standard-size rule (800 A or less), what is the largest permitted overcurrent device?
- a.225 A
- b.250 A✓
- c.300 A
- d.240 A
2026 NEC 240.4(B): when the conductor ampacity does not match a standard rating and the conditions are met, the next higher standard device is permitted. In Table 240.6(A) the next standard size above 240 A is 250 A.2026 NEC §240.4(B)
A 208-V, three-phase feeder supplies a 120,000-VA load. What is the calculated feeder current?
- a.577 A
- b.288 A
- c.333 A✓
- d.200 A
Three-phase current = 120,000 / (1.732 x 208) = 333 A.
A feeder is protected by a 500-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.#2 AWG✓
- b.#3 AWG
- c.#4 AWG
- d.#1 AWG
2026 NEC Table 250.122: for an overcurrent device rated not more than 500 A, the minimum copper equipment grounding conductor is 2 AWG.2026 NEC Table 250.122
A feeder is protected by an 800-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.1/0 AWG✓
- b.#2 AWG
- c.#1 AWG
- d.2/0 AWG
2026 NEC Table 250.122: for an overcurrent device rated not more than 800 A, the minimum copper equipment grounding conductor is 1/0 AWG.2026 NEC Table 250.122
A feeder is protected by a 1,200-A overcurrent device. What is the minimum copper equipment grounding conductor?
- a.3/0 AWG✓
- b.4/0 AWG
- c.#1 AWG
- d.2/0 AWG
2026 NEC Table 250.122: for an overcurrent device rated not more than 1,200 A, the minimum copper equipment grounding conductor is 3/0 AWG.2026 NEC Table 250.122
No exception applies. Which feeder disconnecting means requires ground-fault protection of equipment?
- a.A 1200 A disconnect on a 208Y/120-volt solidly grounded wye system
- b.An 800 A disconnect on a 480Y/277-volt solidly grounded wye system
- c.A 1200 A disconnect on a 480Y/277-volt solidly grounded wye system✓
- d.A 1200 A disconnect on a 480-volt ungrounded delta system
Section 215.10(A) applies to feeder disconnects rated 1000 amperes or more on solidly grounded wye systems with more than 150 volts to ground and not over 1000 volts phase to phase. Only the 1200 ampere, 480Y/277-volt disconnect meets every part of that test. The 208Y/120-volt system is only 120 volts to ground, the 800 ampere device is below the rating threshold, and an ungrounded delta is not a solidly grounded wye.2026 NEC §215.10(A)
What is the minimum size permitted for the grounded conductor of a feeder?
- a.Not smaller than the equipment grounding conductor size required by 250.122✓
- b.Not smaller than the grounding electrode conductor size required by 250.66
- c.Not smaller than the largest ungrounded conductor of that feeder
- d.Not smaller than 1/0 AWG in any feeder
Section 215.4(B) ties the smallest feeder grounded conductor to the equipment grounding conductor size required by 250.122. The grounding electrode conductor table is used for services and separately derived systems, not for this rule. Matching the ungrounded conductors is not required, and 1/0 AWG is a parallel-conductor value from other sections.2026 NEC §215.4(B)
A feeder carries the total load supplied by a set of service conductors. The feeder ampacity must be not less than that of the service conductors when the service conductors have an ampacity of what value or less?
- a.55 amperes✓
- b.60 amperes
- c.100 amperes
- d.125 amperes
Section 215.4(C) applies where the feeder carries the whole load of service conductors that have an ampacity of 55 amperes or less; the feeder may not then be smaller in ampacity than those service conductors. The 60 and 100 ampere values are service disconnect ratings from Article 230, not the threshold in this rule.2026 NEC §215.4(C)
A building has both 480Y/277-volt and 208Y/120-volt systems. Where must each ungrounded feeder conductor be identified by phase or line and by nominal voltage system?
- a.Only at the feeder overcurrent device where it originates
- b.At intervals not exceeding 24 in. along its entire length
- c.Only where the conductor is 4 AWG or larger
- d.At all termination, connection, and splice points✓
Where premises wiring has more than one nominal voltage system, 215.12(C)(2) requires each ungrounded feeder conductor to be identified by phase or line and by system at every termination, connection, and splice point. The 24 in. interval and the 4 AWG break point belong to the dc feeder rules in 215.12(C)(3). Marking only at the source would leave downstream splices unidentified.2026 NEC §215.12(C)(2)
Feeder tap conductors end at a circuit breaker. May the rule that allows the next higher standard overcurrent device rating above the conductor ampacity be used for these tap conductors?
- a.Yes, if the breaker is rated 800 amperes or less
- b.Yes, if the tap conductors are 10 ft long or less
- c.No, it is not permitted for tap conductors✓
- d.Yes, if the taps are in metal raceway
Section 240.21(B) states that the next higher rating allowance of 240.4(B) is not permitted for tap conductors, so the device at the end of the tap may not exceed the tap ampacity. The 800 ampere limit is a condition of that allowance for ordinary circuits, which is the trap. Tap length and wiring method do not change the answer.2026 NEC §240.21(B)
A feeder protected at 300 amperes is tapped to supply a 480-volt to 208-volt transformer under the rule for taps supplying a transformer (primary plus secondary not over 25 ft). What is the minimum ampacity of the secondary conductors?
- a.43.3 A
- b.69.2 A
- c.100 A
- d.230.8 A✓
Section 240.21(B)(3) requires the secondary conductors to have an ampacity of at least the primary-to-secondary voltage ratio times one-third of the feeder overcurrent device rating. One-third of 300 is 100 amperes, and 480 / 208 = 2.308, so 2.308 x 100 = 230.8 amperes. The 100 ampere answer is the primary conductor minimum, and 43.3 amperes inverts the voltage ratio.2026 NEC §240.21(B)(3)
A transformer has a 480-volt primary and a single-phase, 2-wire, 240-volt secondary. The secondary conductors have an ampacity of 200 amperes and no secondary overcurrent device. What is the largest primary overcurrent device value that is considered to protect the secondary conductors?
- a.100 A✓
- b.200 A
- c.250 A
- d.400 A
For a single-phase 2-wire secondary, 240.21(C)(1) lets the primary device protect the secondary conductors if it does not exceed the secondary conductor ampacity times the secondary-to-primary voltage ratio. That is 200 x (240 / 480) = 100 amperes. The 400 ampere answer inverts the ratio, and 250 amperes wrongly applies a 125 percent factor.2026 NEC §240.21(C)(1)
Using the 75 C column, what is the smallest copper conductor rated to carry a 100-A service load?
- a.#2 AWG
- b.#4 AWG
- c.#3 AWG✓
- d.#1 AWG
At 75 C, #4 Cu is rated 85 A and #3 Cu is rated 100 A. The #3 AWG copper is the smallest conductor that meets the 100-A requirement.2026 NEC Table 310.16
Six current-carrying THHN conductors share one raceway. If the 90 C ampacity of #6 Cu is 75 A, what is the adjusted ampacity after the fill adjustment factor for 4-6 conductors?
- a.55 A
- b.60 A✓
- c.52.5 A
- d.75 A
For 4 to 6 current-carrying conductors, apply an 80% adjustment factor: 75 A x 0.80 = 60 A.2026 NEC Table 310.15(C)(1)
A #3 Cu THHN conductor has a 90 C ampacity of 115 A. In a 50 C ambient (correction factor 0.82), what is the corrected ampacity?
- a.94 A✓
- b.82 A
- c.100 A
- d.115 A
Corrected ampacity = 115 A x 0.82 = 94.3 A, about 94 A, before comparing to the termination temperature limit. The 115 A value is the 90 C copper ampacity for 3 AWG in 2026 NEC Table 310.16, and the 0.82 factor comes from Table 310.15(B)(1)(1) for a 90 C conductor in a 46 to 50 C ambient.2026 NEC Table 310.15(B)(1)(1)
A #2 Cu THHN (90 C ampacity 130 A) runs with 6 current-carrying conductors (0.80 factor) in a 40 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?
- a.130 A
- b.95 A✓
- c.104 A
- d.115 A
Apply both factors to the 90 C ampacity: 130 x 0.80 x 0.91 = 94.6 A, about 95 A.2026 NEC §310.15
A one-family dwelling has 2,500 sq ft of habitable floor area. Using the standard method, what is the general lighting and general-use receptacle load before demand factors?
- a.9,000 VA
- b.7,500 VA
- c.6,000 VA
- d.5,000 VA✓
2026 NEC 120.41 figures dwelling general lighting and general-use receptacles at 2 VA per sq ft: 2,500 x 2 = 5,000 VA, calculated before the Table 120.45 demand factors are applied.2026 NEC §120.41
Nine current-carrying #8 THHN conductors share one raceway. If the 90 C ampacity of #8 Cu is 55 A, what is the adjusted ampacity after the fill adjustment factor for 7-9 conductors?
- a.38.5 A✓
- b.44 A
- c.33 A
- d.55 A
2026 NEC Table 310.15(C)(1): 7 to 9 current-carrying conductors take a 70% factor: 55 x 0.70 = 38.5 A.2026 NEC Table 310.15(C)(1)
A #1/0 Cu THHN conductor has a 90 C ampacity of 170 A. In a 46 C ambient (correction factor 0.82), what is the corrected ampacity?
- a.125 A
- b.139 A✓
- c.170 A
- d.150 A
2026 NEC Table 310.15(B)(1)(1): 170 x 0.82 = 139.4 A, about 139 A, before comparison to the termination temperature limit.2026 NEC Table 310.15(B)(1)(1)
A #3 Cu THHN (90 C ampacity 115 A) runs with 8 current-carrying conductors (0.70 factor) in a 38 C ambient (0.91 factor). What is the adjusted-and-corrected ampacity?
- a.73 A✓
- b.80 A
- c.105 A
- d.88 A
Apply both factors to the 90 C ampacity from 2026 NEC Table 310.16: 115 x 0.70 x 0.91 = 73.3 A, about 73 A. The factors come from Table 310.15(C)(1) and Table 310.15(B)(1)(1).2026 NEC Table 310.16
A #6 Cu THHN conductor (90 C ampacity 75 A) is run with twelve current-carrying conductors in one raceway. What is the adjusted ampacity?
- a.45 A
- b.37.5 A✓
- c.52.5 A
- d.26.25 A
2026 NEC Table 310.15(C)(1): 10 to 20 current-carrying conductors take a 50% factor: 75 x 0.50 = 37.5 A.2026 NEC Table 310.15(C)(1)
A retail show window is 30 ft long. Using the show-window unit load, what is the calculated show-window load?
- a.3,000 VA
- b.6,000 VA✓
- c.9,000 VA
- d.5,400 VA
2026 NEC 120.46(A) requires 200 VA per linear foot of show window: 30 x 200 = 6,000 VA.2026 NEC §120.46(A)
An 8,000 sq ft office building is calculated for general lighting using the general lighting unit-load table. What is the general lighting load?
- a.12,000 VA
- b.28,000 VA
- c.8,000 VA
- d.10,400 VA✓
2026 NEC Table 120.42(A) lists 1.3 VA per sq ft for office occupancies: 8,000 x 1.3 = 10,400 VA.2026 NEC Table 120.42(A)