409 questions

Branch Circuits and Conductors

For a circuit rated 100 A or less, conductor ampacity is generally based on which temperature column unless the equipment is listed otherwise?

  • a.90 C
  • b.75 C
  • c.105 C
  • d.60 C✓

Under 110.14(C)(1)(a), terminations for circuits rated 100 A or less are based on the 60 C ampacity unless the equipment is listed and identified for conductors with a higher temperature rating.2026 NEC §110.14(C)(1)(a)

Branch Circuits and Conductors

For circuits rated over 100 A, conductor ampacity for terminations is generally based on which temperature column?

  • a.Nameplate only
  • b.90 C
  • c.75 C✓
  • d.60 C

Under 110.14(C)(1)(b), terminations for circuits rated over 100 A are based on the 75 C ampacity unless the equipment is listed and identified for conductors with a higher temperature rating.2026 NEC §110.14(C)(1)(b)

Branch Circuits and Conductors

Under 2026 NEC 110.14(C), the temperature rating of a conductor used for ampacity at a termination is governed by:

  • a.the ambient temperature where the termination is installed, and nothing else
  • b.the lowest temperature rating of any connected termination, conductor, or device✓
  • c.the 90 C column, in all cases and for every conductor size
  • d.the highest temperature rating of any connected component in the circuit

110.14(C): the conductor ampacity at a termination is based on the lowest temperature rating of any connected termination, conductor, or device. A higher conductor rating, such as 90 C, may still be used for ampacity adjustment and correction.2026 NEC §110.14(C)

Branch Circuits and Conductors

A branch circuit is protected by a 100-A overcurrent device. What is the minimum copper equipment grounding conductor?

  • a.#4 AWG
  • b.#8 AWG✓
  • c.#6 AWG
  • d.#10 AWG

The equipment grounding conductor table requires #8 Cu for an overcurrent device rating up to 100 A.2026 NEC Table 250.122

Branch Circuits and Conductors

Absent a specific exception, what is the maximum overcurrent protection for a #12 Cu conductor?

  • a.20 A✓
  • b.25 A
  • c.30 A
  • d.15 A

Under the small-conductor rule, #12 Cu is limited to a maximum overcurrent device of 20 A.2026 NEC §240.4(D)

Branch Circuits and Conductors

Absent a specific exception, what is the maximum overcurrent protection for a #10 Cu conductor?

  • a.25 A
  • b.40 A
  • c.30 A✓
  • d.20 A

The small-conductor rule limits #10 Cu to a maximum 30-A overcurrent device.2026 NEC §240.4(D)

Branch Circuits and Conductors

A conductor has an ampacity of 115 A, which is not a standard rating. Under the next-standard-size rule (800 A or less), what is the largest permitted overcurrent device?

  • a.125 A✓
  • b.100 A
  • c.110 A
  • d.150 A

When the conductor ampacity does not match a standard rating and the conditions of 240.4(B) are met, the next higher standard rating may be used for devices of 800 A or less. The next standard rating above 115 A is 125 A.2026 NEC §240.4(B)

Branch Circuits and Conductors

A branch circuit is protected by a 60-A overcurrent device. What is the minimum copper equipment grounding conductor?

  • a.#12 AWG
  • b.#8 AWG
  • c.#6 AWG
  • d.#10 AWG✓

2026 NEC Table 250.122: for an overcurrent device rated not more than 60 A, the minimum copper equipment grounding conductor is 10 AWG.2026 NEC Table 250.122

Branch Circuits and Conductors

Absent a specific exception, what is the maximum overcurrent protection for a #14 Cu conductor?

  • a.25 A
  • b.10 A
  • c.20 A
  • d.15 A✓

2026 NEC 240.4(D): under the small-conductor rule, 14 AWG copper is limited to a 15-A overcurrent device.2026 NEC §240.4(D)

Branch Circuits and Conductors

A branch circuit is protected by a 30-A overcurrent device. What is the minimum copper equipment grounding conductor?

  • a.#12 AWG
  • b.#10 AWG✓
  • c.#14 AWG
  • d.#8 AWG

2026 NEC Table 250.122: the table has no 30-A row. A 30-A device is above the 20-A row, so the 60-A row applies and the minimum copper equipment grounding conductor is 10 AWG.2026 NEC Table 250.122

Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →

Branch Circuits and Conductors

On a 4-wire, 3-phase wye feeder where the major portion of the load is nonlinear, the neutral conductor is treated as:

  • a.Not a current-carrying conductor
  • b.A current-carrying conductor✓
  • c.An ignored conductor
  • d.A half current-carrying conductor

Where the major portion of the load on a 4-wire, 3-phase wye circuit is nonlinear, harmonic currents flow in the neutral, so it is counted as a current-carrying conductor when applying the adjustment factors (310.15(E)(1)(3)).2026 NEC §310.15(E)(1)(3)

Branch Circuits and Conductors

A continuous load draws 40 A. At what minimum ampacity must the branch-circuit conductors and overcurrent device be rated?

  • a.50 A✓
  • b.32 A
  • c.40 A
  • d.45 A

A continuous load is taken at 125 percent: 40 A x 1.25 = 50 A. The overcurrent device must be rated at least that (210.20(A)), and the branch-circuit conductors need at least the same ampacity (210.19(A)(1)).2026 NEC §210.20(A)

Branch Circuits and Conductors

What are the commonly recommended maximum voltage-drop limits for a branch circuit and for the combined feeder plus branch circuit?

  • a.2% and 4%
  • b.3% and 5%✓
  • c.5% and 8%
  • d.1% and 3%

The Code's informational notes suggest sizing for no more than 3% drop on a branch circuit and no more than 5% on feeder plus branch circuit combined (210.19 Informational Note and 215.4(A)(2) Informational Note No. 2). These are recommendations, not requirements.2026 NEC §210.19 Informational Note

Branch Circuits and Conductors

A branch circuit that supplies two or more outlets is rated larger than 50 amperes. Which loads may it supply?

  • a.Only nonlighting outlet loads✓
  • b.Only fixed lighting with heavy-duty lampholders
  • c.Any load up to its rating
  • d.Only cooking appliances that are fastened in place

Multiple-outlet branch circuits larger than 50 amperes are limited to nonlighting outlet loads. Fixed lighting with heavy-duty lampholders is a use allowed on 30-, 40- and 50-ampere circuits in other than dwellings, and fastened-in-place cooking appliances describe the 40- and 50-ampere circuit rule. No lighting of any kind may be on a circuit above 50 amperes. See 210.23(E).2026 NEC §210.23(E)

Branch Circuits and Conductors

For an attached garage of a one-family dwelling, which statement gives the required receptacle outlet arrangement?

  • a.One on each wall, no more than 18 in. above the floor
  • b.One for the whole garage, no more than 5 1/2 ft above the floor
  • c.One in each vehicle bay, no more than 6 1/2 ft above the floor
  • d.One in each vehicle bay, no more than 5 1/2 ft above the floor✓

Each attached garage, and each detached garage with electric power, needs at least one receptacle outlet in each vehicle bay, mounted not more than 5 1/2 feet above the floor. A single outlet for the whole garage does not satisfy a multi-bay garage. The 6 1/2 foot height belongs to the outdoor receptacle rule, and there is no per-wall requirement. See 210.52(G)(1).2026 NEC §210.52(G)(1)

Branch Circuits and Conductors

In a dwelling unit, lighting outlets for an interior stairway must be controlled by a wall switch or listed wall-mounted control device at each floor level and each landing with a stairway entry when the stairway has at least how many risers between floor levels?

  • a.Three or more
  • b.Four or more
  • c.Five or more
  • d.Six or more✓

Where lighting outlets are installed for an interior stairway with six or more risers between floor levels, a wall switch or listed wall-mounted control device is required at each floor level and at each landing level that includes a stairway entry. Fewer risers do not trigger this item.2026 NEC §210.70(A)(2)(3)

Branch Circuits and Conductors

AFCI protection is provided by a listed supplemental arc protection circuit breaker at the origin of the branch circuit together with a listed outlet branch-circuit-type AFCI at the first outlet box. With 14 AWG conductors, what is the maximum length of branch-circuit wiring from the overcurrent device to the first outlet?

  • a.25 ft
  • b.50 ft✓
  • c.70 ft
  • d.100 ft

This protection method limits the home run to the first outlet to 50 feet for 14 AWG conductors. The 70 foot limit applies to 12 AWG conductors. The wiring must also be continuous to the outlet AFCI, and the first outlet box must be marked. See 210.12(A).2026 NEC §210.12(A)

Branch Circuits and Conductors

A 30-ampere branch circuit supplies several outlets for utilization equipment. What is the maximum rating of any one cord-and-plug-connected utilization equipment on this circuit?

  • a.12 A
  • b.16 A
  • c.24 A✓
  • d.30 A

On a 30-ampere multiple-outlet circuit, any one cord-and-plug-connected utilization equipment may not exceed 80 percent of the circuit rating: 30 x 0.8 = 24 amperes. The 12 and 16 ampere values are the limits for 15- and 20-ampere receptacles, and 30 amperes would load one appliance to the full circuit rating. Table 210.21(B)(2) shows the same 24 ampere limit for a 30-ampere receptacle. See 210.23(C).2026 NEC §210.23(C)

Branch Circuits and Conductors

A branch circuit carries a 16-ampere continuous load and a 14-ampere noncontinuous load. The overcurrent device is not listed for operation at 100 percent of its rating. What is the minimum standard rating of the branch-circuit overcurrent device?

  • a.30 A
  • b.35 A✓
  • c.40 A
  • d.45 A

The device must be rated for the noncontinuous load plus 125 percent of the continuous load: 14 + (16 x 1.25) = 14 + 20 = 34 amperes. The smallest standard rating that is not less than 34 is 35 amperes. The 30 ampere answer adds the loads with no increase, and 40 amperes applies 125 percent to both loads. See 210.20(A) and Table 240.6(A).2026 NEC §210.20(A)

Branch Circuits and Conductors

Using Column C of Table 120.55 and its notes, what is the demand load for one household electric range with a nameplate rating of 15 kW?

  • a.8 kW
  • b.8.4 kW
  • c.8.8 kW
  • d.9.2 kW✓

Column C gives 8 kW for one range of 12 kW or less. For a range over 12 kW, that value goes up 5 percent for each kW, or major fraction of a kW, above 12. Working: 15 - 12 = 3 kW, 3 x 5 = 15 percent, 8 x 1.15 = 9.2 kW. The lower answers skip the increase or count only one or two of the three extra kilowatts. See Table 120.55, Note 1.2026 NEC Table 120.55

Branch Circuits and Conductors

A dwelling kitchen has a 7.2 kW counter-mounted cooking unit and two 5 kW wall-mounted ovens, all in the same room and supplied by one branch circuit. Using Table 120.55 and its notes, what is the branch-circuit load?

  • a.10 kW✓
  • b.10.4 kW
  • c.14 kW
  • d.17.2 kW

A cooktop and up to two wall ovens on one circuit in the same room are added together and treated as one range: 7.2 + 5 + 5 = 17.2 kW. That is 5.2 kW over 12, and only a major fraction counts as another kW, so the increase is 5 x 5 = 25 percent: 8 x 1.25 = 10 kW. The 10.4 kW answer counts the 0.2 kW as a full step, 14 kW reads Column C for three appliances, and 17.2 kW is the nameplate total. See Table 120.55, Notes 1 and 6.2026 NEC Table 120.55

Electrical Wiring Methods and Electrical Materials

When more than two conductors are pulled into a single conduit, what maximum percent of the conduit's cross-sectional area may they occupy?

  • a.53%
  • b.31%
  • c.60%
  • d.40%✓

2026 NEC Chapter 9, Table 1: over two conductors is limited to 40% fill. Trap: 53% is the limit for one conductor and 31% for exactly two; 60% applies only to short nipples under the notes to the tables.2026 NEC Chapter 9, Table 1

Electrical Wiring Methods and Electrical Materials

A box contains eight #12 AWG conductors and nothing else. Using the box-fill volume allowance, what minimum box volume is required?

  • a.16.0 cu in
  • b.20.0 cu in
  • c.18.0 cu in✓
  • d.22.5 cu in

2026 NEC Table 314.16(B)(4) assigns 2.25 cu in to each #12 conductor: 8 x 2.25 = 18.0 cu in. Trap: 16.0 uses the 2.0 cu in #14 value; 20.0 uses the 2.5 cu in #10 value.2026 NEC Table 314.16(B)(4)

Electrical Wiring Methods and Electrical Materials

A box contains five #12 AWG and three #10 AWG conductors and nothing else. Using the box-fill volume allowances, what minimum box volume is required?

  • a.16.5 cu in
  • b.20.0 cu in
  • c.17.25 cu in
  • d.18.75 cu in✓

2026 NEC Table 314.16(B)(4): #12 = 2.25, #10 = 2.5 cu in. (5 x 2.25) + (3 x 2.5) = 11.25 + 7.5 = 18.75 cu in.2026 NEC Table 314.16(B)(4)

Electrical Wiring Methods and Electrical Materials

A device box has six #12 conductors, one #12 equipment grounding conductor, and one duplex receptacle. Using box-fill rules, what minimum box volume is required?

  • a.22.5 cu in
  • b.15.75 cu in
  • c.20.25 cu in✓
  • d.18.0 cu in

2026 NEC 314.16(B): six conductors count as 6, up to four equipment grounding conductors together count as 1, and the receptacle yoke counts as 2 based on the largest conductor connected to it. (6 + 1 + 2) x 2.25 cu in for #12 from Table 314.16(B)(4) = 20.25 cu in.2026 NEC §314.16(B)

Electrical Wiring Methods and Electrical Materials

A box has internal cable clamps and contains eight #14 AWG conductors. Using box-fill rules, what minimum box volume is required?

  • a.18.0 cu in✓
  • b.22.5 cu in
  • c.20.25 cu in
  • d.16.0 cu in

2026 NEC 314.16(B)(2): where internal clamps are present, add one conductor volume based on the largest conductor. (8 conductors + 1 clamp allowance) x 2.0 cu in for #14 from Table 314.16(B)(4) = 9 x 2.0 = 18.0 cu in.2026 NEC §314.16(B)(2)

Electrical Wiring Methods and Electrical Materials

Under 2026 NEC 110.14(D), terminations that are marked with a tightening torque must be:

  • a.tightened until the conductor visibly deforms under the screw
  • b.tightened to the indicated value using an approved means✓
  • c.left finger-tight so the conductor can expand and contract
  • d.hand-tightened only, with no tool of any kind used

110.14(D): the tightening torque is the value indicated on the equipment or in the manufacturer's installation instructions, and an approved means must be used to reach it. A torque tool is one example of an approved means.2026 NEC §110.14(D)

Electrical Wiring Methods and Electrical Materials

What is the smallest conductor size generally permitted to be installed in parallel?

  • a.1/0 AWG✓
  • b.#1 AWG
  • c.2/0 AWG
  • d.#2 AWG

Conductors are generally permitted in parallel only in sizes 1/0 AWG and larger.2026 NEC §310.10(G)(1)

Electrical Wiring Methods and Electrical Materials

Underground service conductors that are not encased in concrete are buried 24 in. below grade. A warning ribbon must be placed in the trench at least how far above the underground installation?

  • a.12 in.✓
  • b.18 in.
  • c.24 in.
  • d.30 in.

Section 300.7(D)(3) requires a warning ribbon in the trench at least 12 in. above underground service conductors that are not concrete-encased and are buried 18 in. or more below grade. The 18 in. figure is the burial depth that triggers the rule, not the ribbon spacing. The ribbon gives a digger notice before reaching the conductors.2026 NEC §300.7(D)(3)

Electrical Wiring Methods and Electrical Materials

A raceway is installed under metal-corrugated sheet roof decking. What is the minimum clearance required between the lowest surface of the roof decking and the top of the raceway?

  • a.1/2 in.
  • b.3/4 in.
  • c.1-1/4 in.
  • d.1-1/2 in.✓

Section 300.6(E) requires wiring methods under roof decking, metal-corrugated sheet decking included, to be at least 1-1/2 in. below the lowest surface of the decking, so that roofing screws do not reach them. The 1-1/4 in. figure is the setback from the edge of a framing member for bored holes and for runs parallel to framing, which is a different rule.2026 NEC §300.6(E)

Electrical Wiring Methods and Electrical Materials

Inside a duct specifically fabricated for environmental air, flexible metal conduit is used to connect physically adjustable equipment that is permitted in the duct. What is the maximum length of flexible metal conduit allowed for this connection?

  • a.4 ft✓
  • b.10 ft
  • c.15 ft
  • d.25 ft

Section 300.25(B) limits the wiring methods allowed in ducts fabricated for environmental air, and it allows flexible metal conduit only in lengths not over 4 ft to connect physically adjustable equipment and devices permitted in the duct. Longer lengths are not allowed here, even though longer runs of flexible metal conduit are common in other spaces.2026 NEC §300.25(B)

Electrical Wiring Methods and Electrical Materials

A raceway exposed to direct sunlight is mounted 1/2 in. above a rooftop. Before applying the ambient temperature correction factors, how much must be added to the outdoor temperature?

  • a.17°C (30°F)
  • b.22°C (40°F)
  • c.33°C (60°F)✓
  • d.40°C (72°F)

Under 310.15(B)(2), where a raceway or cable is exposed to direct sunlight on or above a rooftop and the distance from the roof to the bottom of the raceway or cable is less than 3/4 in., a temperature adder of 33°C (60°F) is added to the outdoor temperature. The sum is then used to pick the correction factor. At 1/2 in. the raceway is inside the 3/4 in. limit, so the adder applies.2026 NEC §310.15(B)(2)

Electrical Wiring Methods and Electrical Materials

When calculating the maximum number of conductors of the same size permitted in a conduit, the result may be rounded up to the next whole number when the decimal is:

  • a.0.5 or larger
  • b.0.6 or larger
  • c.0.7 or larger
  • d.0.8 or larger✓

Note 7 to the Chapter 9 tables allows the next higher whole number to be used when the calculation for conductors all of the same size gives a decimal of 0.8 or larger. A result such as 12.5 is therefore taken as 12, not 13. Ordinary rounding at 0.5 is the trap.2026 NEC Chapter 9, Notes to Tables, Note 7

Electrical Wiring Methods and Electrical Materials

A trade size 1 rigid metal conduit is bent with a one-shot bender. What is the minimum radius of the bend?

  • a.4 in.
  • b.5-3/4 in.✓
  • c.6 in.
  • d.8 in.

Chapter 9, Table 2 lists a minimum radius of 5-3/4 in. for trade size 1 conduit bent with a one-shot or full-shoe bender. The 6 in. figure in the same row is for other bends, such as those made with a hickey. The 4 in. figure belongs to trade size 1/2.2026 NEC Chapter 9, Table 2

Electrical Wiring Methods and Electrical Materials

A straight run of trade size 2 rigid metal conduit is made up with threaded couplings, and the supports prevent stress from reaching the terminations. What is the maximum distance allowed between supports?

  • a.10 ft
  • b.12 ft
  • c.14 ft
  • d.16 ft✓

Table 344.30(B) allows wider support spacing for straight runs made up with threaded couplings, and it lists 16 ft for trade sizes 2 and 2-1/2. The 10 ft figure is the general rule and also the table value for trade sizes 1/2 and 3/4. The 14 ft value belongs to trade sizes 1-1/4 and 1-1/2.2026 NEC Table 344.30(B)

Electrical Wiring Methods and Electrical Materials

In an office building of Type V construction, which is not a dwelling, Type NM cable is permitted where it is:

  • a.Concealed behind a 15-minute finish-rated thermal barrier✓
  • b.Run exposed along finished walls at any height above the floor
  • c.Laid across the grid of a suspended ceiling above the offices
  • d.Used as service-entrance cable to the building's main panel

For structures other than dwellings that are allowed to be of Type III, IV, or V construction, 334.10(3) requires the cable to be concealed within walls, floors, or ceilings that provide a thermal barrier with at least a 15-minute finish rating. Section 334.12 does not allow the cable exposed in dropped or suspended ceilings in other than dwellings, and it does not allow it as service-entrance cable.2026 NEC §334.10(3)

Electrical Wiring Methods and Electrical Materials

A run of EMT longer than 24 in. will contain three 4 AWG THHN, four 8 AWG THHN, and one 10 AWG THHN equipment grounding conductor. Chapter 9, Table 5 areas are 0.0824 sq in. for 4 AWG, 0.0366 sq in. for 8 AWG, and 0.0211 sq in. for 10 AWG. The 40 percent areas for EMT in Table 4 are 0.213 sq in. for trade size 3/4, 0.346 sq in. for trade size 1, 0.598 sq in. for trade size 1-1/4, and 1.342 sq in. for trade size 2. What is the smallest EMT permitted?

  • a.Trade size 3/4
  • b.Trade size 1
  • c.Trade size 1-1/4✓
  • d.Trade size 2

With more than two conductors the fill limit is 40 percent, and mixed sizes are added from Table 5 with the equipment grounding conductor included. The total is (3 x 0.0824) + (4 x 0.0366) + 0.0211 = 0.2472 + 0.1464 + 0.0211 = 0.4147 sq in. Trade size 1 allows only 0.346 sq in., so trade size 1-1/4 at 0.598 sq in. is the smallest that works. Leaving out the grounding conductor still gives 0.3936 sq in., which is also too much for trade size 1.2026 NEC Chapter 9, Table 4

Electrical Wiring Methods and Electrical Materials

A 60-ft run of rigid metal conduit will contain three 2/0 AWG THHN, three 1/0 AWG THHN, and one 6 AWG THHN. Chapter 9, Table 5 areas are 0.2223 sq in. for 2/0 AWG, 0.1855 sq in. for 1/0 AWG, and 0.0507 sq in. for 6 AWG. The 40 percent areas for RMC in Table 4 are 0.610 sq in. for trade size 1-1/4, 0.829 sq in. for trade size 1-1/2, 1.363 sq in. for trade size 2, and 1.946 sq in. for trade size 2-1/2. What is the smallest RMC permitted?

  • a.Trade size 1-1/4
  • b.Trade size 1-1/2
  • c.Trade size 2✓
  • d.Trade size 2-1/2

More than two conductors means a 40 percent fill limit, and with mixed sizes the Table 5 areas are added. The total is (3 x 0.2223) + (3 x 0.1855) + 0.0507 = 0.6669 + 0.5565 + 0.0507 = 1.2741 sq in. Trade size 1-1/2 allows 0.829 sq in., which is too small, and trade size 2 allows 1.363 sq in., which is enough. Counting only the three largest conductors gives 0.6669 sq in. and wrongly points to trade size 1-1/2.2026 NEC Chapter 9, Table 4

Electrical Wiring Methods and Electrical Materials

An 18-in. trade size 1-1/4 rigid metal conduit nipple connects two cabinets. Chapter 9, Table 4 gives this conduit a total area of 1.526 sq in., a 60 percent area of 0.916 sq in., and a 40 percent area of 0.610 sq in. Each 4 AWG THW conductor has an area of 0.0973 sq in. in Table 5. What is the maximum number of 4 AWG THW conductors permitted in the nipple?

  • a.9✓
  • b.11
  • c.13
  • d.15

A nipple not longer than 24 in. between enclosures may be filled to 60 percent of its total area under Note 4 to the Chapter 9 tables. 0.916 / 0.0973 = 9.41, and because the decimal is below 0.8 the result is taken as 9 conductors. Dividing the full 1.526 sq in. by the conductor area gives 15, which ignores the fill limit. Using the 40 percent area would give only 6.2026 NEC Chapter 9, Notes to Tables, Note 4

Electrical Wiring Methods and Electrical Materials

A long run of trade size 1/2 rigid metal conduit has a 40 percent area of 0.125 sq in. in Chapter 9, Table 4. Each 14 AWG THHN conductor has an area of 0.0097 sq in. in Table 5. Calculating from these tables and their notes, what is the maximum number of 14 AWG THHN conductors permitted?

  • a.9
  • b.12
  • c.13✓
  • d.19

0.125 / 0.0097 = 12.89. Note 7 to the Chapter 9 tables says that for conductors all of the same size, the next higher whole number is used when the decimal is 0.8 or larger, so 12.89 becomes 13. Dropping the decimal to get 12 misses that note. The answer 19 comes from the 60 percent area, which is only for nipples 24 in. or shorter.2026 NEC Chapter 9, Table 1 and Notes to Tables, Note 7

Electrical Wiring Methods and Electrical Materials

A pull box is used for an angle pull of 500 kcmil conductors. Two trade size 3 raceways and one trade size 2 raceway enter the same wall in a single row. What is the minimum distance from that wall to the opposite wall of the box?

  • a.18 in.
  • b.23 in.✓
  • c.24 in.
  • d.26 in.

For an angle pull with 4 AWG or larger conductors, 314.28(A)(2) requires six times the trade size of the largest raceway, plus the sum of the trade sizes of the other raceways in the same row on the same wall. That is (6 x 3) + 3 + 2 = 23 in. The 18 in. answer forgets the other two raceways. The 24 in. answer uses the eight-times rule, which is for straight pulls.2026 NEC §314.28(A)(2)

Electrical Wiring Methods and Electrical Materials

In a pull box, 3/0 AWG conductors enter through a trade size 2-1/2 raceway in one wall and leave through a trade size 2 raceway in the adjacent wall. What is the minimum distance between these two raceway entries?

  • a.12 in.
  • b.15 in.✓
  • c.20 in.
  • d.27 in.

Section 314.28(A)(2) requires the distance between raceway entries that enclose the same conductor to be at least six times the trade size of the larger raceway. 6 x 2-1/2 = 15 in. Using the smaller raceway gives 12 in., which is too short. Adding the two trade sizes before multiplying gives 27 in., which is not what the rule says.2026 NEC §314.28(A)(2)

Electrical Wiring Methods and Electrical Materials

Six current-carrying 8 AWG THHN copper conductors share a raceway in a 38°C ambient. All terminations are rated 75°C. Table 310.16 lists 8 AWG copper at 50 A in the 75°C column and 55 A in the 90°C column. The 90°C correction factor for 36 to 40°C is 0.91, and the adjustment factor for 4 to 6 conductors is 80 percent. What is the allowable ampacity of each conductor?

  • a.About 35 A
  • b.About 40 A✓
  • c.About 44 A
  • d.About 50 A

Section 310.15 lets correction and adjustment start from the ampacity for the conductor's own temperature rating, so begin with the 90°C value: 55 x 0.91 x 0.80 = 40.04 A. This is below the 50 A allowed by the 75°C terminations, so about 40 A governs. Stopping at the 75°C column gives 50 A and skips both factors. Applying only the 80 percent factor gives 44 A and skips the temperature correction.2026 NEC §310.15

Electrical Wiring Methods and Electrical Materials

Three current-carrying 3 AWG THWN-2 copper conductors are in a raceway exposed to direct sunlight, 1/2 in. above a rooftop, where the outdoor temperature is 35°C. A raceway less than 3/4 in. above the roof takes a 33°C adder. Table 310.16 lists 3 AWG copper at 100 A (75°C) and 115 A (90°C). The 90°C correction factors are 0.96 for 31 to 35°C and 0.58 for 66 to 70°C. With 75°C terminations, what is the allowable ampacity?

  • a.33.0 A
  • b.66.7 A✓
  • c.100.0 A
  • d.110.4 A

The raceway is closer than 3/4 in. to the roof, so 33°C is added to the outdoor temperature: 35 + 33 = 68°C. The 90°C factor for that range is 0.58, and 115 x 0.58 = 66.7 A. That is below the 100 A allowed at the 75°C terminations, so 66.7 A governs. The 110.4 A answer uses the factor for 35°C and leaves out the rooftop adder.2026 NEC §310.15(B)(2)

Electrical Wiring Methods and Electrical Materials

Two 208Y/120-volt, 3-phase, 4-wire feeders share one raceway in a 30°C ambient. Each feeder has three ungrounded conductors and a neutral, all 1/0 AWG THHN copper, and the major portion of the load is nonlinear. Table 310.16 lists 1/0 AWG copper at 150 A (75°C) and 170 A (90°C). Adjustment factors are 80 percent for 4 to 6 conductors and 70 percent for 7 to 9. With 75°C terminations, what is the allowable ampacity of each conductor?

  • a.119 A✓
  • b.136 A
  • c.150 A
  • d.170 A

Under 310.15(E), the neutral of a 4-wire, 3-phase wye circuit counts as a current-carrying conductor when the major portion of the load is nonlinear. That makes eight current-carrying conductors, so the 70 percent factor applies: 170 x 0.70 = 119 A, which is below the 150 A limit of the 75°C terminations. The 136 A answer counts only the six ungrounded conductors and uses 80 percent.2026 NEC §310.15(E)

Electrical Equipment and Devices

A 75-kVA transformer has a 90-A primary current (over 9 A). With primary-only protection at 125% max, what is the primary overcurrent device rating (next higher standard permitted)?

  • a.150 A
  • b.100 A
  • c.125 A✓
  • d.110 A

2026 NEC Table 450.5(B) allows primary-only protection at 125% of primary current when that current is 9 A or more: 90 x 1.25 = 112.5 A. That is not a standard rating, so Note 1 to the table permits the next higher standard rating, 125 A. Trap: 110 A is the next lower standard rating.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

A 75-kVA transformer with a 208-A secondary (over 9 A) is protected on both the primary and the secondary. What is the maximum secondary overcurrent device (next higher standard permitted)?

  • a.300 A✓
  • b.260 A
  • c.250 A
  • d.225 A

2026 NEC Table 450.5(B) allows up to 125% on the secondary where both sides are protected: 208 x 1.25 = 260 A. Since 260 A is not a standard rating, Note 1 to the table permits the next higher standard rating, 300 A. Trap: 250 A is the next lower standard rating.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

A 45-kVA, 480-V, three-phase transformer (primary FLC 54 A, over 9 A) has primary-only overcurrent protection at 125% maximum. What is the primary device rating (next higher standard permitted)?

  • a.60 A
  • b.80 A
  • c.70 A✓
  • d.90 A

2026 NEC Table 450.5(B): 125% of 54 A = 67.5 A; that is not a standard size, so the next higher standard device, 70 A, is permitted for primary-only protection.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

A 150-kVA, 480-208Y/120-V transformer (secondary FLC 416 A) is protected on both sides. What is the maximum secondary overcurrent device at 125% (next higher standard permitted)?

  • a.450 A
  • b.600 A✓
  • c.500 A
  • d.520 A

2026 NEC Table 450.5(B): 416 x 1.25 = 520 A on the secondary. That is not a standard rating, so Note 1 to the table permits the next higher standard rating, 600 A.2026 NEC Table 450.5(B)

Electrical Equipment and Devices

For equipment operating at 0-150 V to ground under Condition 1, what is the minimum depth of working space in front of the equipment?

  • a.4 ft
  • b.2.5 ft
  • c.2 ft
  • d.3 ft✓

Table 110.26(A)(1) sets a minimum working depth of 3 ft for 0-150 V to ground under Condition 1 (live parts on one side, no live or grounded parts on the other).2026 NEC Table 110.26(A)(1)