Texas Master Electrician Exam — All Questions
The figures these questions turn on, pooled by value and printable, with a side to write them from memory: Texas Master Electrician (TDLR / PSI, 2026 NEC) cheat sheet PDF — $9.99 →
409 questions
Class II, Group F covers combustible carbonaceous dusts whose total entrapped volatiles exceed what percentage?
- a.8 percent✓
- b.12 percent
- c.20 percent
- d.40 percent
Section 500.6(B) defines Group F as combustible carbonaceous dusts having more than 8 percent total entrapped volatiles. The larger percentages are not found in the group definition.2026 NEC §500.6(B)
In which locations is the dusttight protection technique permitted?
- a.Class II, Division 1 or 2 only
- b.Class II, Division 2 and Class III, Division 1 or 2✓
- c.Class I, Division 2 and Class II, Division 2
- d.Any Class I, II, or III location
Section 500.7(C) permits dusttight equipment in Class II, Division 2 and in Class III, Division 1 or 2. Class II, Division 1 calls for the dust-ignitionproof technique instead, so a choice that includes it is wrong. Dusttight is not a recognized technique for Class I gas or vapor locations.2026 NEC §500.7(C)
In a restricted industrial establishment, a gas detection system allows Class I, Division 2 equipment in an area that is Division 1 only because of inadequate ventilation. The alarm must activate at a gas concentration of not more than:
- a.10 percent of the lower flammable limit
- b.20 percent of the lower flammable limit
- c.40 percent of the lower flammable limit✓
- d.60 percent of the lower flammable limit
Section 500.7(K)(2) requires the gas detection alarm, audible or visual or both, to operate at no more than 40 percent of the lower flammable limit when detection is used to offset inadequate ventilation. The 20 percent figure belongs to a different case, the first alarm for a building interior that opens into a Division 2 area. A 60 percent setting would be above the permitted maximum.2026 NEC §500.7(K)(2)
Unless it is identified for low-temperature service, explosionproof equipment may not be used where the ambient temperature is below:
- a.-40°C (-40°F)
- b.-25°C (-13°F)✓
- c.-10°C (14°F)
- d.0°C (32°F)
Section 500.8 does not allow explosionproof or dust-ignitionproof equipment in ambient temperatures below -25°C (-13°F) unless the equipment is identified for low-temperature service. The freezing point and -10°C are warmer than the actual limit, and -40°C is colder than the limit the Code sets.2026 NEC §500.8
A pressure transmitter relies on a single diaphragm to keep flammable process fluid out of its electrical compartment. It is mounted in an unclassified location. What must the transmitter be identified for?
- a.General-purpose use only
- b.A Class I, Division 1 location
- c.A Class II, Division 2 location
- d.A Class I, Division 2 location✓
Section 500.8(B)(4) requires equipment that depends on a single compression seal, diaphragm, or tube to keep process fluid out to be identified for Class I, Division 2, even when it sits in an unclassified location. General-purpose equipment ignores the chance that the single seal fails. Division 1 is more than the rule asks, and Class II deals with dust.2026 NEC §500.8(B)(4)
A luminaire for a Class I location has a maximum surface temperature of 135°C (275°F). Which temperature class marking matches that value?
- a.T3
- b.T4✓
- c.T5
- d.T6
Table 500.8(C)(4) pairs a maximum surface temperature of 135°C (275°F) with temperature class T4. T3 is the 200°C row, T5 is the 100°C row, and T6 is the 85°C row.2026 NEC Table 500.8(C)(4)
In a Class I, Division 2 location, a 4 ft length of listed LFMC with fittings listed for grounding supplies an instrument circuit. For the wire-type equipment bonding jumper to be omitted, overcurrent protection in the circuit must be limited to no more than:
- a.10 amperes✓
- b.15 amperes
- c.20 amperes
- d.30 amperes
Section 500.30(C)(2) lets the bonding jumper be left out in Division 2 only when three conditions are all met: listed LFMC of 6 ft or less with fittings listed for grounding, overcurrent protection of 10 amperes or less, and a load that is part of a meter, instrument, or relay circuit. The 15, 20, and 30 ampere choices are common branch-circuit ratings but exceed the limit.2026 NEC §500.30(C)(2)
With a suitable gas group and temperature class, which Zone-marked equipment does Article 501 permit in a Class I, Division 1 location?
- a.Zone 0, Zone 1, or Zone 2 equipment
- b.Zone 0 or Zone 1 equipment
- c.Zone 0 equipment only✓
- d.No Zone-marked equipment
Section 501.5 permits Zone 0 equipment in Class I, Division 1 or Division 2 locations. Equipment marked for Zone 0, 1, or 2 is accepted only in Division 2, so Zone 1 and Zone 2 equipment cannot be used in Division 1 under this section. Saying no Zone equipment is allowed ignores the section altogether.2026 NEC §501.5
The Class I, Division 2 wiring method table lists Schedule 80 PVC conduit under which condition?
- a.Only in restricted industrial establishments where metal conduit lacks corrosion resistance✓
- b.In any Division 2 location where the conduit is exposed to physical damage
- c.In any commercial occupancy where the conduit run is under 50 ft
- d.Wherever flexible connections to vibrating equipment are needed
Table 501.10(B)(1) lists Schedule 80 PVC for Class I, Division 2 only in restricted industrial establishments, and only where metal conduit would not provide enough corrosion resistance. Exposure to physical damage, a short run, or a need for flexibility are not conditions that open the door to PVC in this table.2026 NEC Table 501.10(B)(1)
In a Class I, Division 1 location, a conduit enters an explosionproof enclosure that contains only splices. A conduit seal is required at that entry when the conduit is at least what size?
- a.Trade size 1
- b.Trade size 1-1/2
- c.Trade size 2✓
- d.Trade size 3
Section 501.15(A)(1) requires a seal at an entry to an explosionproof enclosure holding terminals, splices, or taps when the entry is trade size 2 (metric designator 53) or larger. Smaller entries to a splice-only enclosure do not trigger this rule, and waiting until trade size 3 would leave a trade size 2 entry unsealed.2026 NEC §501.15(A)(1)
Want these explained in order? Texas Master Electrician Exam — Open-Book Study Guide (2026 NEC) — PDF + EPUB, $14.99 · 14-day refund →
In Class I, Division 1, a conduit entry to an explosionproof enclosure must be sealed when the enclosed apparatus can, in normal operation, exceed what share of the autoignition temperature (in degrees Celsius) of the gas involved?
- a.80 percent✓
- b.90 percent
- c.100 percent
- d.125 percent
Section 501.15(A)(1) calls for a seal where the enclosure holds apparatus that may produce arcs, sparks, or temperatures above 80 percent of the autoignition temperature, in degrees Celsius, of the gas or vapor. The higher percentages would let equipment run much closer to, or past, the ignition point before a seal was required.2026 NEC §501.15(A)(1)
Two explosionproof enclosures in a Class I, Division 1 location are joined by a conduit nipple, and one seal placed within 18 in. of each enclosure is to serve both. What is the longest nipple permitted for this arrangement?
- a.12 in.
- b.18 in.
- c.24 in.
- d.36 in.✓
Section 501.15(A)(3) allows a single seal to serve two explosionproof enclosures joined by a nipple or conduit run of not more than 36 in., provided the seal is no more than 18 in. from either enclosure. The 18 in. figure is the seal distance, not the nipple length, and 12 in. and 24 in. are not the limit stated.2026 NEC §501.15(A)(3)
Unless a seal is specifically identified for a higher fill, the conductors in a conduit seal may occupy no more than what share of the cross-sectional area of a rigid metal conduit of the same trade size?
- a.25 percent✓
- b.31 percent
- c.40 percent
- d.53 percent
Section 501.15(C)(6) limits the conductors in a seal to 25 percent of the cross-sectional area of rigid metal conduit of the same trade size, unless the seal is identified for more. The 31, 40, and 53 percent choices all allow more conductor area than this section does, which would leave too little room for compound to surround each conductor.2026 NEC §501.15(C)(6)
In a repair garage, a Class I liquid that is not a motor fuel is dispensed from a drum. The Class I, Division 2 location extends in all directions how far from the dispensing point?
- a.18 in.
- b.3 ft✓
- c.5 ft
- d.10 ft
Section 511.5(B) makes the space within 3 ft (900 mm) of any fill or dispensing point for Class I liquids other than fuels, measured in every direction, a Class I, Division 2 location. Eighteen inches falls short of that boundary, and 5 ft and 10 ft overstate it.2026 NEC §511.5(B)
A stock room beside a classified repair garage area is not likely to have flammable vapors released in it. If mechanical ventilation is the method relied on, what minimum rate allows the stock room to be unclassified?
- a.Two air changes per hour
- b.Four air changes per hour✓
- c.Six air changes per hour
- d.Twelve air changes per hour
Section 511.5(E)(1) treats adjacent areas such as stock rooms and switchboard rooms as unclassified when they are mechanically ventilated at four or more air changes per hour. Positive air pressure or an unpierced partition are the other ways to qualify. Two air changes is below the minimum, and six or twelve are more than the section requires.2026 NEC §511.5(E)(1)
A normal branch-circuit panelboard and an essential branch-circuit panelboard serve the same patient care vicinity. Their equipment grounding terminal buses must be connected together with an insulated continuous copper conductor no smaller than:
- a.12 AWG
- b.10 AWG✓
- c.8 AWG
- d.6 AWG
Section 517.14 requires the equipment grounding terminal buses of the normal and essential panelboards serving the same patient care vicinity to be tied together with an insulated continuous copper conductor not smaller than 10 AWG. A 12 AWG conductor is too small, and 8 AWG or 6 AWG is larger than the stated minimum.2026 NEC §517.14
An isolated ground receptacle is installed in a patient care space but outside the patient care vicinity. How must the equipment grounding conductor connected to its grounding terminal be identified along its entire length?
- a.Green insulation with one or more yellow stripes✓
- b.Green insulation with no stripes of any other color
- c.Bare copper marked with green tape at terminations
- d.White insulation with a green stripe
Section 517.16(B)(1) requires the conductor on the grounding terminal of an isolated ground receptacle in a patient care space to be insulated and identified its whole length by green insulation with one or more yellow stripes. Plain green with no stripes is the marking for the other equipment grounding conductor, the one that serves the box and fixed equipment. Bare copper and white insulation do not meet either rule.2026 NEC §517.16(B)(1)
A hospital with Category 1 spaces has ground-fault protection of equipment on its service disconnecting means. What additional ground-fault protection does the Code require?
- a.Nothing more; one level at the service is sufficient
- b.Ground-fault protection on the load side of each transfer switch
- c.Ground-fault protection between the generator and transfer switch
- d.Another level of ground-fault protection in each next-level feeder disconnect✓
Section 517.17(B) requires a second step of ground-fault protection in every next-level feeder disconnecting means downstream toward the load whenever the service or feeder disconnect has such protection. The same section says this protection is not required between on-site power sources and essential system transfer switches or on the load side of those switches. A single level at the service is not enough for these buildings.2026 NEC §517.17(B)
Measured from the end of the cord, including bared leads, to the face of the attachment plug cap, what is the longest overall length permitted for a mobile home feeder assembly?
- a.36 1/2 ft✓
- b.21 ft
- c.25 ft
- d.50 ft
The overall cord length has to fall between 21 ft and 36 1/2 ft, so 36 1/2 ft is the upper limit. The 21 ft figure is the minimum overall length, not the maximum, and the other values do not appear in the rule. See 550.10(D).2026 NEC §550.10(D)
A receptacle outlet is installed on the underside of a mobile home for pipe heating cable. It must be located within what distance of the cold water inlet?
- a.10 ft
- b.2 ft✓
- c.18 in.
- d.36 in.
The heat tape outlet goes within 2 ft of the cold water inlet so the cable can reach without an extension cord. The 36 in. figure belongs to the bathroom basin receptacle rule, and the other distances are not in this rule. See 550.13(G).2026 NEC §550.13(G)
A mobile home's wiring is given a dielectric strength test between live parts and ground that lasts one full minute. What test voltage applies?
- a.480 volts
- b.900 volts✓
- c.1500 volts
- d.2400 volts
The one-minute dielectric test is run at 900 volts between live parts and the grounding means. A shorter one-second test is allowed only at a higher voltage, so the larger figures do not match the one-minute test, and 480 volts is too low. See 550.19(A).2026 NEC §550.19(A)
Supply conductors from an RV generator must terminate in a panelboard, enclosed transfer switch, or junction box with a receptacle located within what distance of the point where they enter the vehicle?
- a.18 in.✓
- b.3 ft
- c.6 ft
- d.10 ft
The generator supply conductors have to land in a panelboard, enclosed transfer switch, or junction box within 18 in. of where they enter the vehicle. The longer distances would leave too much unprotected conductor run inside the vehicle. See 551.30(E).2026 NEC §551.30(E)
Service equipment for a floating dock must be located on land. What is the closest horizontal distance it may be to the structure it serves?
- a.10 ft
- b.20 ft
- c.50 ft
- d.5 ft✓
The service equipment sits on land, adjacent to the structure, but no closer than 5 ft horizontally and not on or in the structure itself. The larger distances are more than the rule requires. See 555.17.2026 NEC §555.17
In a boatyard, outside the yard areas used for moving vessels or stepping masts, overhead branch-circuit and feeder wiring must be at least how high above grade?
- a.10 ft
- b.12 ft
- c.18 ft✓
- d.20 ft
Overhead wiring in the other parts of a boatyard must clear grade by at least 18 ft. The 20 ft figure is the horizontal setback from the edge of the vessel-moving areas, not a height, and the lower values are ordinary clearances that do not apply here. See 555.34(B)(2).2026 NEC §555.34(B)(2)
A marina has more than three receptacles supplying shore power to boats. What must be available at the facility?
- a.A second disconnecting means located on the pier
- b.A listed leakage current measurement device✓
- c.A portable generator sized for the largest receptacle
- d.An isolation transformer for each shore power receptacle
Once more than three receptacles supply shore power, a listed leakage current measurement device has to be on hand so stray current from a boat can be found. The other items are not required by this rule. See 555.35(E).2026 NEC §555.35(E)
An electric pool water heater with resistance elements must have its elements subdivided into loads of not more than:
- a.30 amperes, protected at not over 40 amperes
- b.60 amperes, protected at not over 80 amperes
- c.80 amperes, protected at not over 100 amperes
- d.48 amperes, protected at not over 60 amperes✓
Resistance pool heaters have their elements split into loads of 48 amperes or less, each protected at 60 amperes or less. The other pairs use numbers that are not in the rule. See 680.10(A)(1).2026 NEC §680.10(A)(1)
A variable-speed pool pump motor is run by an adjustable-speed drive. Where is the required ground-fault protection NOT permitted to be installed?
- a.In the panelboard that supplies the drive
- b.Between the drive output and the motor✓
- c.At the outlet on the line side of the drive
- d.In the branch circuit ahead of the drive disconnect
The ground-fault device may not sit between the output terminals of the drive and the motor. The other three locations are all on the supply side of the drive, which is where the protection belongs. See 680.21(C)(2).2026 NEC §680.21(C)(2)
A wall-mounted underwater pool luminaire that is not listed for a lesser depth must have the top of its lens at least how far below the normal water level?
- a.4 in.
- b.6 in.
- c.8 in.
- d.18 in.✓
Unless the luminaire is listed and identified for shallower use, the top of the lens goes at least 18 in. below the normal water level. Four inches is the absolute floor that applies even to luminaires listed for lesser depths, so it is not the answer for an ordinary luminaire. See 680.23(A)(5).2026 NEC §680.23(A)(5)
A pool junction box has three conduit entries, each run extending directly to a forming shell. What is the fewest grounding terminals the box may have?
- a.Four✓
- b.Three
- c.Five
- d.Six
The box needs at least one more grounding terminal than it has conduit entries, so three entries call for four terminals. Three terminals forgets the extra one, and the larger counts are more than the minimum. See 680.24(D)(1).2026 NEC §680.24(D)(1)
A solidly grounded wye emergency system of more than 150 volts to ground has circuit-protective devices rated 1000 amperes or more. What is the highest ground-fault current setting allowed for its ground-fault signal devices?
- a.1200 amperes✓
- b.800 amperes
- c.1000 amperes
- d.2000 amperes
The ground-fault signal devices may be set no higher than 1200 amperes of ground-fault current. The 1000 ampere figure is the protective device rating that triggers the requirement, not the setting limit. See 700.7(D).2026 NEC §700.7(D)
Storage batteries used to supply emergency illumination must be able to carry the total load for at least:
- a.30 minutes
- b.2 hours
- c.4 hours
- d.1 1/2 hours✓
Batteries and UPS equipment feeding emergency illumination must hold the full load for at least 1 1/2 hours. Two hours is the general minimum for other emergency power sources, which is the usual mix-up. See 700.12(B)(4).2026 NEC §700.12(B)(4)
In a building with an occupied floor more than 75 ft above fire department vehicle access, an emergency feeder raceway is protected only by concrete encasement, with no engineer's documentation of a fire rating. What is the least concrete thickness allowed around the raceway?
- a.2 in.
- b.5 in.✓
- c.3 in.
- d.12 in.
Concrete encasement by itself must be at least 5 in. thick measured from every point on the raceway. The 2 in. thickness is accepted only when a licensed engineer documents that the installation gives a 2-hour rating. See 700.10(D)(2).2026 NEC §700.10(D)(2)
Which type of transfer equipment is not permitted to be used for an emergency system?
- a.Bypass-isolation transfer switches
- b.Meter-mounted transfer switches✓
- c.Electrically operated transfer switches
- d.Mechanically held transfer switches
Meter-mounted transfer switches may not be used on emergency systems. Automatic transfer switches for emergency use are in fact required to be electrically operated and mechanically held, and bypass-isolation equipment is a recognized way to service them. See 700.6(A).2026 NEC §700.6(A)
An optional standby generator is connected to its load by a manual transfer switch. The system must have enough capacity to supply:
- a.Only the largest single piece of equipment
- b.The full connected load of the premises
- c.125 percent of the largest motor load
- d.All equipment intended to be operated at one time✓
With manual or nonautomatic transfer, the standby source only has to carry the equipment meant to run at the same time, and the user may choose that load. It does not have to carry everything on the premises, and sizing to the single largest item or a motor percentage is not the rule. See 702.4(A)(1).2026 NEC §702.4(A)(1)
One alternate source supplies emergency, legally required standby, and optional standby loads through a load management system. Which loads get first priority for power?
- a.Emergency circuits✓
- b.Optional standby circuits
- c.Legally required standby circuits
- d.The largest motor circuits
Load management must keep power to emergency circuits first, then legally required standby circuits, then optional standby circuits. Motor size has nothing to do with the priority order. See 700.5(C).2026 NEC §700.5(C)
A mobile home measures 80 ft by 15 ft outside, coupler excluded. Using 3 VA per square foot at 120 volts, how many 15-ampere lighting circuits are required?
- a.Two✓
- b.One
- c.Three
- d.Four
Area is 80 x 15 = 1200 sq ft, and 1200 x 3 VA = 3600 VA. Dividing by 120 volts gives 30 amperes, and 30 / 15 = 2 circuits. One circuit comes from skipping part of the load or assuming a larger circuit, and three or four come from arithmetic slips. See 550.12(A).2026 NEC §550.12(A)
An RV has a total connected 12-volt load of 60 amperes. Sizing the converter at 100 percent of the first 20 amperes, 50 percent of the second 20 amperes, and 25 percent of the load above 40 amperes, what is the minimum converter output rating?
- a.30 amperes
- b.45 amperes
- c.35 amperes✓
- d.60 amperes
First 20 A at 100 percent is 20 A, the second 20 A at 50 percent is 10 A, and the remaining 20 A at 25 percent is 5 A, for a total of 35 A. Sixty amperes ignores the demand steps, 30 A takes half of everything, and 45 A applies the wrong percentage to the last step. See 551.20(C).2026 NEC §551.20(C)
A 15-ampere branch circuit in a mobile home supplies lighting outlets and also a fixed appliance. What is the largest total rating of fixed appliances allowed on that circuit?
- a.10 amperes
- b.12 amperes
- c.15 amperes
- d.7.5 amperes✓
When lighting outlets are on the same circuit, fixed appliances may total no more than 50 percent of the circuit rating. 15 x 0.50 = 7.5 amperes. Twelve amperes uses the 80 percent figure for motor or continuous loads, and 15 amperes is allowed only when there are no lighting outlets on the circuit. See 550.12(D).2026 NEC §550.12(D)
An electric pool water heater has a total nameplate-rated load of 40 amperes. What is the minimum ampacity of its branch-circuit conductors?
- a.50 amperes✓
- b.32 amperes
- c.40 amperes
- d.60 amperes
Conductors and overcurrent devices for an electric pool water heater are sized at 125 percent of the total nameplate load or more. 40 x 1.25 = 50 amperes. Forty amperes applies no multiplier, 32 amperes multiplies by 80 percent instead, and 60 amperes uses 150 percent. See 680.10(A)(2).2026 NEC §680.10(A)(2)
A battery system supplies emergency lighting on a 120-volt nominal circuit. During the required discharge period, the voltage applied to the load may not fall below:
- a.96 volts
- b.105 volts✓
- c.108 volts
- d.114 volts
The voltage at the load may not drop below 87 1/2 percent of nominal. 120 x 0.875 = 105 volts. The other values come from using 80, 90, or 95 percent, none of which is the figure in the rule. See 700.12(B)(4).2026 NEC §700.12(B)(4)
After rapid shutdown is initiated, controlled conductors located outside the array boundary must be limited to what level?
- a.Not more than 30 volts within 30 seconds✓
- b.Not more than 80 volts within 30 seconds
- c.Not more than 30 volts within 10 seconds
- d.Not more than 80 volts within 10 seconds
Outside the array boundary, or more than 1 m (3 ft) from where the conductors enter the building, controlled conductors must drop to 30 volts or less within 30 seconds of initiation. The 80 volt figure belongs to conductors inside the array boundary. The 10 second answers use a time that this rule does not give. See 690.12(B)(1).2026 NEC §690.12(B)(1)
Three PV modules are connected in parallel in one PV source circuit. Each module has a highest short-circuit current rating of 12 A. Using the 125% method, what is the maximum current of this PV source circuit?
- a.15 A
- b.36 A
- c.45 A✓
- d.56.25 A
Under the 125% method, the maximum current is the sum of the parallel modules' short-circuit current ratings multiplied by 125%. Here 3 x 12 A = 36 A, and 36 A x 1.25 = 45 A. 36 A leaves out the 125%, 15 A applies it to only one module, and 56.25 A applies it twice. See 690.8(A)(1)(a)(1).2026 NEC §690.8(A)(1)(a)(1)
A building has several PV systems, each with rapid shutdown, connected to a single service. What is the largest number of rapid shutdown initiation devices permitted, grouped together?
- a.Two
- b.Four
- c.Six✓
- d.Eight
Where multiple PV systems with rapid shutdown are on a single service, the initiation devices are limited to six and they must be grouped. Two and four are below the limit the rule sets, and eight is over it. See 690.12(C)(3).2026 NEC §690.12(C)(3)
A licensed professional electrical engineer supplies a documented and stamped design that calculates maximum PV source circuit current from simulated local irradiance. The 125% method gives 50 A for the same circuit. What is the lowest current value the engineered calculation may use?
- a.35 A✓
- b.40 A
- c.50 A
- d.62.5 A
An engineered current calculation is allowed, but it may not be less than 70% of the value found by the 125% method. 50 A x 0.70 = 35 A. 40 A uses 80%, 50 A assumes no reduction is allowed, and 62.5 A adds another 125% that this rule does not call for. See 690.8(A)(1)(a)(3).2026 NEC §690.8(A)(1)(a)(3)
On the building label that shows where the rapid shutdown initiation devices are, what is the minimum height of the capitalized title letters?
- a.9.5 mm (3/8 in.)✓
- b.13 mm (1/2 in.)
- c.19 mm (3/4 in.)
- d.25 mm (1 in.)
The title on the rapid shutdown label must be in capital letters at least 9.5 mm (3/8 in.) high, with legible text that contrasts with the background. The larger sizes are more than the rule asks for and are not the stated minimum. See 690.12(D).2026 NEC §690.12(D)
One 30 A overcurrent device protects three parallel-connected PV string circuits. Each string has a maximum current of 9 A calculated under 690.8(A)(1)(a). What is the minimum ampacity required for each string conductor?
- a.27 A
- b.30 A
- c.39 A
- d.48 A✓
When one overcurrent device protects more than one parallel string, each string conductor must carry at least the device rating plus the maximum currents of the other strings on that device. That is 30 A + 9 A + 9 A = 48 A. 30 A counts only the device, 39 A adds only one of the two other strings, and 27 A is just the three string currents added together. See 690.8(D).2026 NEC §690.8(D)
What access is required for the overcurrent devices that protect PV system dc circuits?
- a.Readily accessible in every installation
- b.Accessible, but not necessarily readily accessible✓
- c.Within sight of the inverter they supply
- d.At grade level outside the building
PV dc overcurrent devices must be accessible, but the Code says they do not have to be readily accessible, which allows them in places such as rooftop combiners. Requiring ready access overstates the rule. The within-sight and grade-level answers describe conditions this section does not impose. See 690.9(C).2026 NEC §690.9(C)
A PV circuit has a maximum current of 16 A calculated under 690.8(A). The overcurrent device is not part of an assembly listed for continuous operation at 100% of its rating. Before rounding up to a standard size, what is the minimum overcurrent device rating?
- a.12.8 A
- b.16 A
- c.20 A✓
- d.25 A
A PV overcurrent device that is not in a 100% rated assembly must be rated at least 125% of the maximum current. 16 A x 1.25 = 20 A. 16 A would be right only for a 100% rated assembly, 12.8 A applies 80% in the wrong direction, and 25 A applies the 125% twice. See 690.9(B)(1).2026 NEC §690.9(B)(1)
A calculation made under Article 690 produces a result of 12.4. Using the rounding that the article permits, what value may be used?
- a.12✓
- b.12.5
- c.13
- d.15
Article 690 calculations may be rounded to the nearest whole number, and a fraction smaller than 0.5 may be dropped. Since 0.4 is less than 0.5, 12.4 becomes 12. Rounding up to 13 would apply only at 0.5 or more, and 12.5 and 15 are not whole-number rounding at all. See 690.4(G).2026 NEC §690.4(G)
For applying Article 690, the output of an ac module is treated as which type of circuit?
- a.A PV source circuit
- b.A PV dc circuit
- c.A dc-to-dc converter circuit
- d.An inverter output circuit✓
An ac module has its inverter built in, so its output is treated as an inverter output circuit. The PV source circuit rules do not apply to ac modules, and the other two answers are dc circuits that an ac module does not present to the installer. See 690.6(A) and 690.6(B).2026 NEC §690.6(B)