PrepPass team · Verified against Texas Department of Licensing and Regulation (TDLR) · How we review

Free · printable · no signup

Texas Master Electrician Exam Cheat Sheet (2026)

A free, printable Texas Master Electrician exam cheat sheet: the 197 highest-yield points to know, grouped into 10 sections that follow the exam's content areas.

  • Free to read, print and keep — no signup, no email, no paywall.
  • 197 of the 197 points carry a citation to the rule they come from.
  • The real Texas Master Electrician exam: 108 questions · 320 minutes · 70% on each portion to pass.
  • Prints from your browser (Ctrl-P, or Cmd-P on a Mac) — the navigation, buttons and links drop out of the printed copy.
  • 409 free Texas Master Electrician practice questions on the same material, every one explained.
Studying in order?

Practice stays free. The full Texas Master Electrician (TDLR / PSI, 2026 NEC) study guide is the material itself, taught start to finish — a downloadable PDF + EPUB you keep.

Get the book — $14.99

Definitions, Theory and Plans

Study →
Demand factor
Maximum demand divided by total connected load, always 1 or less.· 2026 NEC Article 100
Approval
Conductors and equipment are acceptable only if approved by the authority having jurisdiction.· 2026 NEC §110.2
Listing instructions
Listed or labeled equipment is installed and used according to the instructions in its listing or labeling.· 2026 NEC §110.3(B)
Two entrances for large equipment
Equipment rated 1200 amperes or more and over 6 ft wide needs an entrance at each end, each at least 24 in. wide and 6 1/2 ft high.· 2026 NEC §110.26(C)(2)
Personnel doors
Within 25 ft of the working space of equipment rated 800 amperes or more, doors open in the direction of egress with listed panic or fire exit hardware.· 2026 NEC §110.26(C)(3)
Arc-flash label
Shows system voltage, arc flash boundary, incident energy or minimum PPE level, and the assessment date.· 2026 NEC §110.16
Terminations over 100 amperes
Higher-rated conductors are used at their 75 degrees C ampacity unless the equipment is listed and identified otherwise.· 2026 NEC §110.14(C)(1)
Dwelling general lighting
Calculated at 2 VA per sq ft before demand factors.· 2026 NEC §120.41
Small-appliance and laundry circuits
Each is included at 1,500 VA.· 2026 NEC §120.52
Lighting demand factors
Dwellings take the first 3,000 VA at 100 percent and the remainder at 35 percent; hotels and warehouses have their own steps.· 2026 NEC Table 120.45
Receptacle demand
First 10 kVA at 100 percent and the remainder at 50 percent.· 2026 NEC Table 120.47
Neutral reduction
Unbalanced load above 200 amperes may be taken at 70 percent where the conditions are met.· 2026 NEC §120.61(B)

Services, Service Equipment and Separately Derived Systems

Study →
Continuous load test
Ampacity of at least the noncontinuous load plus 125 percent of the continuous load.· 2026 NEC §230.42(A)(1)
After-correction test
Ampacity remaining after adjustment and correction must be at least the maximum load served.· 2026 NEC §230.42(A)(2)
Dwelling 83 percent allowance
A 200-ampere dwelling service may use 2/0 copper.· 2026 NEC §310.12
Largest motor
Taken at 125 percent, so 25 percent of its full-load current is added.· 2026 NEC §430.24
Optional dwelling method
First 8 kVA of general load at 100 percent and the remainder at 40 percent.· 2026 NEC §120.82(B)
Central space heating
Included at 65 percent of nameplate under the optional method.· 2026 NEC §120.82(C)
Multifamily optional method
Limited to buildings with three or more dwelling units that meet the stated conditions.· 2026 NEC §120.84
Dryer load
Nameplate rating or 5,000 VA, whichever is larger.· 2026 NEC §120.54
Neutral above 200 amperes
The portion over 200 amperes may be taken at 70 percent.· 2026 NEC §120.61(B)(2)
GFPE setting and delay
Maximum setting of 1200 amperes, and no more than one second of delay at 3000 amperes or more.· 2026 NEC §230.95(C)
GFPE testing
Performance tested when first installed, by primary current injection, with a written record.· 2026 NEC §230.95(E)
Available fault current marking
Field marked on non-dwelling service equipment with the date of the calculation.· 2026 NEC §110.24(A)
Arc-flash marking
Permanent marking on non-dwelling service and feeder-supplied equipment likely to be serviced while energized.· 2026 NEC §110.16
Purpose of system grounding
Limits voltage from lightning, surges and contact with higher-voltage lines, and stabilizes voltage to earth.· 2026 NEC §250.4(A)(1)
GEC table
Sized by the ungrounded service conductors, for example 2/0 copper for over 600 through 1,100 kcmil.· 2026 NEC Table 250.66
Rod, pipe or plate cap
The conductor to these electrodes alone need not exceed 6 AWG copper.· 2026 NEC §250.66(A)
Concrete-encased cap
The conductor to this electrode alone need not exceed 4 AWG copper.· 2026 NEC §250.66(B)
Main bonding jumper
From the bonding table up to 1,100 kcmil copper, then 12.5 percent of the ungrounded conductor area.· 2026 NEC §250.28(D)(1)
Grounded service conductor minimum
Not smaller than the bonding table value for the ungrounded conductors.· 2026 NEC §250.24(D)(1)
Water pipe bonding jumper
Sized from the same bonding table by the service conductors.· 2026 NEC §250.104(A)(1)
Green bonding screw
A screw-only bonding jumper has a green finish visible when installed.· 2026 NEC §250.28(B)
Supply-side bonding jumper
A wire-type jumper is sized from the bonding table by the derived conductors.· 2026 NEC §250.30(A)(2)
Derived system GEC
Connects the grounded conductor to the electrode and is sized from Table 250.66 by the derived conductors.· 2026 NEC §250.30(A)(5)
Common GEC
A wire-type common conductor serving several systems is at least 3/0 AWG copper.· 2026 NEC §250.30(A)(6)
10-ft secondary conductors
Ampacity not less than the calculated load and the rating of the device or bus they supply.· 2026 NEC §240.21(C)(2)

Feeder Design: Demand Loads, Motor Feeders, Taps and Transformers

Study →
Conductor ampacity
At least 125 percent of the continuous load plus the noncontinuous load.· 2026 NEC §215.4(A)(1)
Device rating
At least 125 percent of the continuous load plus the noncontinuous load, rounded up to a standard size.· 2026 NEC §215.5
Next standard size
A device of 800 amperes or less may be the next standard rating above the conductor ampacity.· 2026 NEC §240.4(B)
Lighting demand
First 3,000 VA at 100 percent and the remainder at 35 percent, applied to the combined lighting, small-appliance and laundry load.· 2026 NEC Table 120.45
Range demand and Note 1
Use Column C by number of ranges, plus 5 percent for each kW over 12.· 2026 NEC Table 120.55
Dryer demand
Three to five dryers at 80 percent, six at 75 percent.· 2026 NEC Table 120.54
Fastened-in-place appliances
Four or more on the same dwelling feeder may be taken at 75 percent.· 2026 NEC §120.53
Optional dwelling general loads
100 percent of the first 8 kVA and 40 percent of the remainder.· 2026 NEC §120.82(B)
Optional heating and cooling
Include only the largest of the listed heating and cooling values, with central electric heat at 65 percent.· 2026 NEC §120.82(C)
Multifamily factor
One demand factor by unit count is applied to the connected load; 46 to 50 units is 26 percent.· 2026 NEC Table 120.84(C)
Receptacle demand
First 10 kVA at 100 percent, remainder at 50 percent.· 2026 NEC Table 120.47
Commercial kitchen equipment
Six or more units are taken at 65 percent, not less than the two largest units combined.· 2026 NEC Table 120.56
Motor feeder conductors
125 percent of the largest motor full-load current plus the sum of the other motors.· 2026 NEC §430.24
Motor feeder protection
Not more than the largest motor branch device plus the other full-load currents; choose the standard size at or below that sum.· 2026 NEC §430.62(A)
10-foot tap
Ampacity at least one-tenth of the feeder device rating and not less than the load served.· 2026 NEC §240.21(B)(1)
25-foot tap
Ampacity at least one-third of the feeder device rating.· 2026 NEC §240.21(B)(2)
Transformer tap secondary
Secondary ampacity is at least the primary-to-secondary voltage ratio times one-third of the feeder device rating.· 2026 NEC §240.21(B)(3)
Primary-only protection
On a single-phase 2-wire secondary the primary device may protect the secondary conductors when limited by the voltage ratio.· 2026 NEC §240.21(C)(1)
No next size up
The next higher standard rating is not permitted for tap conductors.· 2026 NEC §240.21(B)
Range neutral
The neutral load for household ranges may be taken at 70 percent of the range demand.· 2026 NEC §120.61(B)(1)
Neutral over 200 amperes
The portion of unbalanced load above 200 amperes is taken at 70 percent.· 2026 NEC §120.61(B)(2)
Minimum grounded conductor
Not smaller than the equipment grounding conductor required for the feeder.· 2026 NEC §215.4(B)
Feeder to a separate building
Run an equipment grounding conductor with the feeder and keep the neutral isolated at the building.· 2026 NEC §250.32(B)(1)
Equipment grounding conductor
Size from the rating of the feeder overcurrent device.· 2026 NEC Table 250.122

Branch-Circuit Design: Ampacity, Terminations and Protection

Study →
Lowest rating governs
Ampacity at a termination is based on the lowest temperature rating of any connected termination, conductor or device.· 2026 NEC §110.14(C)
100 amperes or less
Use the 60 degree C ampacity unless the equipment is listed and identified for higher.· 2026 NEC §110.14(C)(1)(a)
Over 100 amperes
Use the 75 degree C ampacity unless the equipment is listed and identified for higher.· 2026 NEC §110.14(C)(1)(b)
Ambient correction
Multiply the table ampacity by the factor for the ambient range, such as 0.82 for 46 to 50 degrees C on a 90 degree C conductor.· 2026 NEC Table 310.15(B)(1)(1)
Conductor-count adjustment
80 percent for 4 to 6, 70 percent for 7 to 9, 50 percent for 10 to 20 current-carrying conductors.· 2026 NEC Table 310.15(C)(1)
Both factors together
Where both conditions exist, apply both factors to the insulation-column ampacity.· 2026 NEC §310.15
Nonlinear neutral
The neutral of a 4-wire wye circuit with mostly nonlinear load counts as current-carrying.· 2026 NEC §310.15(E)
Small conductors
14, 12 and 10 AWG copper are limited to 15-, 20- and 30-ampere devices.· 2026 NEC §240.4(D)
Next standard size
Up to 800 amperes, the next standard device above the conductor ampacity is permitted when the conditions are met.· 2026 NEC §240.4(B)
Continuous load
Device rating is at least the noncontinuous load plus 125 percent of the continuous load.· 2026 NEC §210.20(A)
Equipment grounding conductor
Use the row at or above the device rating; a 30-ampere device reads the 60-ampere row.· 2026 NEC Table 250.122
Dwelling unit load
2 VA per square foot covers general lighting and general-use receptacles.· 2026 NEC §120.41
Office lighting
The general lighting unit load for offices is 1.3 VA per square foot.· 2026 NEC Table 120.42(A)
Show windows
200 VA per linear foot.· 2026 NEC §120.46(A)
Cooking appliance notes
Add 5 percent per kW or major fraction over 12, and combine a cooktop with up to two wall ovens on one circuit as one range.· 2026 NEC Table 120.55
30-ampere circuit
One cord-and-plug appliance may not exceed 80 percent of the circuit rating.· 2026 NEC §210.23(C)
Above 50 amperes
Multiple-outlet circuits supply only nonlighting outlet loads.· 2026 NEC §210.23(E)
AFCI home-run length
With the supplemental breaker plus outlet AFCI method, the run to the first outlet is at most 50 feet for 14 AWG and 70 feet for 12 AWG.· 2026 NEC §210.12(A)
Voltage-drop guidance
3 percent for the branch circuit and 5 percent overall are recommendations only.· 2026 NEC §210.19 Informational Note
Garage receptacles
One per vehicle bay, at most 5 1/2 feet above the floor.· 2026 NEC §210.52(G)(1)

Wiring Methods and Materials

Study →
Fill limit
More than two conductors may occupy no more than 40 percent of the raceway area.· 2026 NEC Chapter 9, Table 1
Mixed sizes
Add the individual conductor areas, grounding conductor included, and compare the sum with the raceway's 40 percent area.· 2026 NEC Chapter 9, Table 4
Nipple fill
A nipple 24 inches or shorter between enclosures may be filled to 60 percent of its total area.· 2026 NEC Chapter 9, Notes to Tables, Note 4
Rounding
For same-size conductors, the count goes up to the next whole number only at a decimal of 0.8 or larger.· 2026 NEC Chapter 9, Notes to Tables, Note 7
Order of operations
Correct and adjust from the conductor's own temperature rating, then cap the result at the termination rating.· 2026 NEC §310.15
Rooftop adder
A sunlit raceway less than 3/4 inch above a roof takes 33°C added to the outdoor temperature before correction.· 2026 NEC §310.15(B)(2)
Neutral with nonlinear load
The neutral of a 4-wire wye circuit counts as current-carrying when most of the load is nonlinear.· 2026 NEC §310.15(E)
Volume allowances
Each conductor is counted at the cubic-inch allowance for its own size.· 2026 NEC Table 314.16(B)(4)
Internal clamps
Internal cable clamps add one allowance based on the largest conductor in the box.· 2026 NEC §314.16(B)(2)
Angle pulls
Use six times the largest raceway plus the other raceways in the row, and six times the larger raceway between entries for the same conductor.· 2026 NEC §314.28(A)(2)
RMC support spacing
Straight runs with threaded couplings may be supported at wider intervals by trade size, 16 feet for sizes 2 and 2-1/2.· 2026 NEC Table 344.30(B)
FMC in air ducts
Flexible metal conduit in a fabricated environmental-air duct is limited to 4 feet for adjustable equipment.· 2026 NEC §300.25(B)
NM in non-dwellings
In Type III, IV or V non-dwelling buildings, NM cable is concealed behind a 15-minute finish-rated thermal barrier.· 2026 NEC §334.10(3)
Parallel conductors
Conductors are generally paralleled only in sizes 1/0 AWG and larger.· 2026 NEC §310.10(G)(1)
Torque
Terminations with a marked torque are tightened to that value by an approved means.· 2026 NEC §110.14(D)

Electrical Equipment and Devices

Study →
125 percent limit
At 9 amperes or more, primary-only protection and the secondary device of a both-sides scheme are each limited to 125 percent of that side's current.· 2026 NEC Table 450.5(B)
Next standard size
Where 125 percent is not a standard rating, the next higher standard rating is permitted, and the standard sizes come from the ratings table.· 2026 NEC Table 240.6(A)
Depth
Depth is 3 feet at 0 to 150 volts to ground, and 3, 3-1/2 or 4 feet by condition at 151 to 600 volts to ground.· 2026 NEC Table 110.26(A)(1)
Width
At least 30 inches or the equipment width, whichever is greater, with 90-degree door opening.· 2026 NEC §110.26(A)(2)
Headroom
At least 6.5 feet or the height of the equipment, whichever is greater.· 2026 NEC §110.26(A)(3)
No storage
Required working space is kept clear and is not used for storage.· 2026 NEC §110.26(B)
Dedicated space
The equipment footprint is reserved from floor to 6 feet above the equipment or the structural ceiling if lower.· 2026 NEC §110.26(E)(1)(a)
Entrance at each end
Equipment rated 1,200 amperes or more and over 6 feet wide needs entrance and egress at each end of the working space.· 2026 NEC §110.26(C)(2)
Personnel doors
Doors within 25 feet of the working space of equipment rated 800 amperes or more open in the direction of egress with listed panic or fire exit hardware.· 2026 NEC §110.26(C)(3)
Panelboard protection
The overcurrent device protecting a panelboard is rated no more than the panelboard.· 2026 NEC §408.36
Circuit directory
Each circuit and modification is legibly identified by its specific purpose in the panel directory.· 2026 NEC §408.4(A)
Tub and shower zone
No receptacles within 3 feet horizontally or 8 feet vertically of a tub or shower.· 2026 NEC §406.9(C)(1)
Faceplate thickness
Metal faceplates are at least 0.030 inch if ferrous and 0.040 inch if nonferrous.· 2026 NEC §406.16(A)
Receptacle screws
Use the screws supplied with the listed receptacle or machine screws with 32 threads per inch.· 2026 NEC §406.14
Box depth behind equipment
Where equipment projects more than 1-7/8 inches rearward, the box is at least the equipment depth plus 1/4 inch.· 2026 NEC §314.24(B)(1)
Heavy luminaires
A luminaire over 50 pounds is supported independently unless the box is listed for the weight.· 2026 NEC §314.27(A)(2)

Motors, Compressors and Generators: Designing the Complete Circuit

Study →
General motors
Table full-load current sizes the conductors and short-circuit protection, and nameplate current sizes separate overloads.· 2026 NEC §430.6(A)(1)
Torque motors
The nameplate locked-rotor current is the rated current for sizing branch-circuit conductors.· 2026 NEC §430.6(B)
Three-phase table values
At 460 volts the table lists 34 A for 25 hp and 65 A for 50 hp.· 2026 NEC Table 430.250
Single motor
Branch-circuit conductors carry at least 125 percent of the table full-load current.· 2026 NEC §430.22
Dc motor on a rectifier
Conductors from a single-phase full-wave rectifier are sized at 150 percent, and half-wave at 190 percent.· 2026 NEC §430.22(A)
Wye-start, delta-run
Conductors between the controller and the motor are sized at 72 percent of full-load current.· 2026 NEC §430.22(C)
Duty-cycle service
Intermittent duty with a 15-minute rated motor uses 85 percent of nameplate current.· 2026 NEC Table 430.22(E)
Table percentages
Squirrel-cage motors: 175 percent dual-element fuse, 250 percent inverse-time breaker, 300 percent non-time-delay fuse.· 2026 NEC Table 430.52(C)(1)
Starting ceiling
An inverse-time breaker may be raised to no more than 400 percent where full-load current is 100 A or less, with no rounding above that.· 2026 NEC §430.52(C)(1)
Separate overload
125 percent of nameplate with a 1.15 service factor or a 40 degree C rise marking, 115 percent for all other motors.· 2026 NEC §430.32(A)(1)
Integral protector
170, 156 or 140 percent of table full-load current depending on the size of that current.· 2026 NEC §430.32(A)(2)
Overload units
A three-phase ac motor needs three overload units, one in each phase.· 2026 NEC Table 430.37
Feeder device ceiling
Largest branch device plus the other motors' full-load currents, rounded down to a standard rating.· 2026 NEC §430.62(A)
Feeder conductors
125 percent of the highest-rated motor plus 100 percent of the rest.· 2026 NEC §430.24
Single compressor conductors
At least 125 percent of the rated-load or branch-circuit selection current.· 2026 NEC §440.32
Compressor plus other motors
Sum of the currents plus 25 percent of the largest.· 2026 NEC §440.33
Compressor protection
The device starts at 175 percent of rated-load current, and rounding up depends on an exception.· 2026 NEC §440.22(A)
Equipment nameplate
The marked minimum circuit ampacity sizes the supply conductors.· 2026 NEC §440.4(B)
Generator conductors
At least 115 percent of the generator nameplate current rating.· 2026 NEC §445.13(A)

Control Devices and Disconnecting Means: Selection, Rating and Layout

Study →
Controller poles
A controller that is not the disconnect need not open all conductors to the motor.· 2026 NEC §430.84
Slash-rated controller
Permitted only on solidly grounded circuits within both the line-to-ground and line-to-line voltage numbers.· 2026 NEC §430.83(E)
Marking of purpose
Each disconnecting means is marked with its purpose unless the purpose is evident from its location and arrangement.· 2026 NEC §110.22(A)
Manual motor controller
Usable as the disconnect only if additionally marked as suitable as a motor disconnect.· 2026 NEC §430.109(A)(6)
Small stationary motors
A general-use switch rated at least twice the full-load current is permitted for 2 hp or less at 300 volts or less.· 2026 NEC §430.109(C)(1)
Very large motors
Above 100 hp ac or 40 hp dc, a general-use or isolating switch must be marked not to be operated under load.· 2026 NEC §430.109(E)
Controller disconnect location
In sight from the controller location.· 2026 NEC §430.102(A)
Accessibility
At least one of the disconnecting means in a motor circuit must be readily accessible.· 2026 NEC §430.107
Single motor
Disconnect ampere rating at least 115 percent of motor full-load current.· 2026 NEC §430.110(A)
Combination load
At least 115 percent of the sum of all currents at full load, resistance loads included.· 2026 NEC §430.110(C)(2)
Small motor locked-rotor current
Assumed to be six times full-load current when the motor is not in the tables.· 2026 NEC §430.110(C)(3)
Single compressor
115 percent of the greater of rated-load current or branch-circuit selection current.· 2026 NEC §440.12(A)(1)
Combination HVAC load
115 percent of the sum of all currents at the rated-load condition.· 2026 NEC §440.12(B)(2)
Location
Within sight from and readily accessible from the equipment.· 2026 NEC §440.14
Split-system marking
The outdoor disconnect is marked with the location of all indoor units it supplies, outside one- and two-family dwellings.· 2026 NEC §440.15
Dwelling service disconnect
Readily accessible outdoor location on or within sight of the dwelling.· 2026 NEC §230.70(A)(1)
Combined rating
Ratings of multiple service breakers may be added to reach the required minimum.· 2026 NEC §230.80
Inaccessible feeder device
Load-side branch devices must be readily accessible and rated lower than the feeder device.· 2026 NEC §225.40
Emergency disconnect marking
Red background, white text, letters at least 1/2 in. high on the outside front.· 2026 NEC §225.41(C)
Power-operated breaker
Must be able to be opened by hand if its power supply fails.· 2026 NEC §230.76

Special Occupancies, Equipment and Conditions

Study →
Gas groups by safe gap
A gas other than acetylene with a safe gap of 0.45 mm or less is Group B.· 2026 NEC §500.6(A)
Ammonia room
Detection must start the ventilation at 150 ppm or less for the room to be unclassified.· 2026 NEC §500.5(A)(2)
Gas detection alarm
The alarm must operate at no more than 40 percent of the lower flammable limit.· 2026 NEC §500.7(K)(2)
Metal dust
Group E dust is Class II, Division 1 whether present normally or abnormally.· 2026 NEC §500.5(C)(1)
Adjacent garage areas
Four air changes per hour lets an adjacent stock room be unclassified.· 2026 NEC §511.5(E)(1)
Division 2 wiring methods
Type MC with listed fittings is accepted, and Schedule 80 PVC only in restricted industrial sites with corrosion concerns.· 2026 NEC Table 501.10(B)(1)
Single-seal process equipment
Equipment relying on one diaphragm or seal must be identified for Class I, Division 2.· 2026 NEC §500.8(B)(4)
Seal at enclosures
Seal within 18 in. of arcing or hot equipment, using the 80 percent autoignition test.· 2026 NEC §501.15(A)(1)
Boundary seal
Seal within 10 ft of the Division 1 boundary with no ordinary fittings in between.· 2026 NEC §501.15(A)(4)
Zone equipment
Only Zone 0 equipment may be used in a Class I, Division 1 location.· 2026 NEC §501.5
Two grounding paths
Patient care branch circuits need an insulated copper grounding conductor plus a qualifying metal raceway or armor.· 2026 NEC §517.13
Panelboard bus bonding
Normal and essential panel grounding buses are tied with 10 AWG or larger insulated copper.· 2026 NEC §517.14
Isolated ground identification
The isolated grounding conductor is green with one or more yellow stripes for its full length.· 2026 NEC §517.16(B)(1)
Second level of protection
Each next-level feeder disconnect needs its own ground-fault protection.· 2026 NEC §517.17(B)
RV converter sizing
Apply 100, 50 and 25 percent to the first 20 A, second 20 A and remainder of the 12-volt load.· 2026 NEC §551.20(C)
Dielectric test
The one-minute test between live parts and ground is run at 900 volts.· 2026 NEC §550.19(A)
Boatyard overhead wiring
Outside the vessel-moving areas, overhead wiring must be at least 18 ft above grade.· 2026 NEC §555.34(B)(2)
Leakage measurement
More than three shore power receptacles triggers a listed leakage current measurement device.· 2026 NEC §555.35(E)
Luminaires over the pool
New luminaires over the pool are mounted at least 12 ft above maximum water level.· 2026 NEC §680.22(B)(1)
Low-voltage limit
Sinusoidal ac underwater luminaires above 15 volts require GFCI protection.· 2026 NEC §680.23(A)(3)
Drive-fed pump
Ground-fault protection may not be placed between the drive output and the motor.· 2026 NEC §680.21(C)(2)
Perimeter bonding
The bonded perimeter surface extends 3 ft horizontally beyond the inside pool walls.· 2026 NEC §680.26(B)(2)
Restoration time
Emergency power must be available within 10 seconds of losing the normal source.· 2026 NEC §700.12
Battery performance
Batteries carry the load 1 1/2 hours without the load voltage dropping below 87 1/2 percent of nominal.· 2026 NEC §700.12(B)(4)
Concrete encasement
Concrete alone must be 5 in. thick around the emergency feeder raceway in a tall building.· 2026 NEC §700.10(D)(2)
Ground-fault signal setting
The signal devices may be set at no more than 1200 amperes.· 2026 NEC §700.7(D)
Load priority
Emergency loads take priority over legally required and optional standby loads.· 2026 NEC §700.5(C)

Renewable Energy Technologies: Photovoltaics and EV Chargers

Study →
Emergency shutoff
At non-dwelling sites the shutoff is in sight of the equipment and 20 ft to 100 ft away.· 2026 NEC §625.43(D)(1)
Receptacle on branch circuit
A 50-ampere EVSE receptacle is not permitted on a 40-ampere branch circuit.· 2026 NEC §625.44
Power export receptacle
Export equipment receptacles are limited to 250 volts single phase and 50 amperes.· 2026 NEC §625.60(B)
Coupler height
Outdoor coupling means are stored at least 24 in. above grade unless listed and marked otherwise.· 2026 NEC §625.50
GFCI
All receptacles for EV charging require GFCI protection for personnel.· 2026 NEC §625.54
125 percent method
Maximum current is the sum of parallel module short-circuit currents times 125 percent.· 2026 NEC §690.8(A)(1)(a)(1)
Engineered method floor
A stamped engineered calculation may not be less than 70 percent of the 125 percent method value.· 2026 NEC §690.8(A)(1)(a)(3)
Rounding
Article 690 results may be rounded to the nearest whole number, dropping fractions below 0.5.· 2026 NEC §690.4(G)
Common-return conductor
Ampacity is at least the sum of the overcurrent device ratings of the circuits sharing it.· 2026 NEC §690.8(C)
Strings on one device
Each string conductor carries the device rating plus the maximum currents of the other strings.· 2026 NEC §690.8(D)
Device rating
A device not in a 100 percent rated assembly is rated at least 125 percent of maximum current.· 2026 NEC §690.9(B)(1)
Protection at one end
Allowed inside a building for runs up to 10 ft in raceway or metal-clad cable.· 2026 NEC §690.9(A)(3)
Device access
PV dc overcurrent devices must be accessible but need not be readily accessible.· 2026 NEC §690.9(C)
Series converters
Without listing instructions, maximum voltage is the sum of the converters' maximum rated output voltages.· 2026 NEC §690.7(B)(2)
AC module output
The output of an ac module is treated as an inverter output circuit.· 2026 NEC §690.6(B)
Voltage after shutdown
Controlled conductors outside the array boundary reach 30 volts or less within 30 seconds.· 2026 NEC §690.12(B)(1)
Multiple systems
On a single service, initiation devices are limited to six and must be grouped.· 2026 NEC §690.12(C)(3)
Label lettering
The label title is in capitals at least 3/8 in. high.· 2026 NEC §690.12(D)
Interactive equipment
Interconnection equipment must be listed or field labeled for the interactive function.· 2026 NEC §705.2